Installation
‐
Refrigerant
Filling
24
NOTICE
The
chiller
will
require
more
coolant
than
the
volumes
listed
above
to
fill
the
chiller
internal
plumbing,
plasma
cutting
system
internal
plumbing,
and
the
connecting
hoses.
After
the
pumps
have
been
started
for
the
first
time,
additional
coolant
will
likely
be
required
as
the
internal
system
components
are
filled
with
coolant.
When
the
chiller’s
controller
is
powered,
the
coolant
reservoir
level
can
be
monitored
via
the
controller
(refer
to
Section
8.5).
6.10
Refrigerant
Filling
If
the
chiller
is
installed
in
a
fluorinated
gas
import
restricted
country
or
the
European
Union,
it
is
subject
to
the
F
‐
gas
regulations.
For
these
applications
the
DTS
chiller
part
number
802092
is
shipped
with
a
nitrogen
charge
and
has
no
refrigerant.
Prior
to
startup
the
chiller
is
required
to
be
charged
with
refrigerant.
DTS
can
support
charging
the
refrigeration
through
its
certified
contractor
network.
For
DTS
service
information
refer
to
Section
12.
6.11
Installation
Checklist
Transport
and
Location
of
Chiller
Unpack
and
check
received
chiller.
Sufficient
clearance
for
intake
and
exhaust
air
has
been
maintained
around
the
chiller.
Sufficient
clearance
for
service
access
has
been
maintained
around
the
chiller.
Electrical
Supply
voltage,
current,
phase,
and
frequency
match
chiller’s
requirement.
Incoming
main
power
is
wired
correctly.
Incoming
power
ground
wire
is
connected
to
ground
lug
on
electrical
panel.
Chiller
has
been
energized
(main
circuit
breaker
disconnect
turned
to
ON
position)
for
at
least
8
hours
prior
to
first
run
(refer
to
section
7.1).
Electrical
service
conforms
to
all
applicable
national
and
local
codes.
Change
frequency
setpoint
on
the
controller
if
installed
in
a
50Hz
country
(see
Figure
31
in
Section
8.7)
Plumbing
Supply
and
return
connections
are
correct
for
both
cooling
circuits.
Plumbing
is
not
dead
‐
headed:
no
kinks
in
hoses,
valves
between
chiller
and
plasma
system
are
fully
opened,
etc.)
Plumbing
has
been
checked
for
leaks.
Coolant
reservoir
is
filled
with
the
correct
quality
and
to
the
correct
level.
Hypertherm, Inc. Part Number: 810540
Summary of Contents for Koolant Koolers N-Series
Page 61: ...Appendix B Electrical Schematics PLC 59 PLC Hypertherm Inc Part Number 810540...
Page 62: ...Appendix B Electrical Schematics I O Module 60 I O Module Hypertherm Inc Part Number 810540...
Page 63: ...Appendix B Electrical Schematics Logic 61 Logic Hypertherm Inc Part Number 810540...
Page 73: ...Appendix E Declaration of Conformity 71 Hypertherm Inc Part Number 810540...
Page 74: ...Appendix E Declaration of Conformity 72 Hypertherm Inc Part Number 810540...
Page 75: ...Appendix E Declaration of Conformity 73 Hypertherm Inc Part Number 810540...