Troubleshooting
‐
Alarm
List
45
Alarm
Code
Alarm
Name
Type
Description
Corrective
Action
Verify
the
chiller
is
operating
within
the
specified
environment
conditions
(refer
to
Section
5.2.1).
Verify
that
air
intake
and
exhaust
clearances
have
been
adhered
to
(refer
to
Section
5.2.5).
Verify
the
compressor
status
is
“ON”
(refer
to
Figure
21).
Verify
the
motorized
hot
gas
valve
is
fully
closed
(0%)
(refer
to
Figure
21).
Verify
the
Superheat
is
<
20°F
(refer
to
Figure
15).
If
the
Superheat
is
>
20°F
the
refrigerant
charge
may
be
low.
Contact
DTS
Service.
AL*024
Fluid
Under
Temp
Fault
Auto
reset
Process
water
outlet
temperature
is
<
10°F
(5.6°C)
below
its
setpoint.
Verify
the
tank
heater
status
is
“ON”
(refer
to
Figure
24).
Verify
the
compressor
status
is
“OFF”
(refer
to
Figure
21).
Contact
DTS
Service
AL*025
Tank
Level
Low
Auto
reset
The
coolant
reservoir
level
is
low,
but
pumps
are
operable.
Refill
the
coolant
reservoir
(refer
to
Section
6.9).
AL*026
Tank
Critically
Low
Auto
reset
The
coolant
reservoir
level
is
too
low
to
safely
operate
the
pumps.
Refill
the
coolant
reservoir
(refer
to
Section
6.9).
AL*027
Low
Pressure
Fault
Auto
reset
The
refrigeration
circuit
suction
pressure
has
gone
too
low.
Verify
the
chiller
is
operating
within
the
specified
environment
conditions
(refer
to
Section
5.2.1).
Verify
the
Superheat
is
<
20°F
(refer
to
Figure
15).
If
the
Superheat
is
>
20°F
the
refrigerant
charge
may
be
low.
Contact
DTS
Service.
AL*028
Process
Flow
Fault
User
reset
The
process
coolant
flow
rate
is
below
the
minimum
threshold
0f
0.4GPM
Verify
that
all
valves
in
the
process
fluid
circuit
are
open.
Verify
that
there
are
no
kinks
or
other
obstructions
in
the
process
fluid
hoses.
Verify
that
the
fluid
reservoir
is
not
low.
Check
the
Process
circuit
fluid
filter
to
ensure
the
filter
is
clean.
If
the
filter
is
contaminated
replace
the
filter
(refer
to
Section
10.2).
Reset
the
alarms
(refer
to
Section
8.2.3)
and
restart
the
chiller.
If
the
fault
persists
contact
DTS
Service.
AL*029
Recirc
Flow
Fault
User
reset
The
flow
rate
in
the
recirculation
circuit
is
below
the
minimum
threshold
of
6GPM.
Check
the
Process
circuit
fluid
filter
to
ensure
the
filter
is
clean.
If
the
filter
is
contaminated
replace
the
filter
(refer
to
Section
10.2).
Fully
open
the
globe
valve
at
the
outlet
of
the
recirculation
pump.
Reset
the
alarms
(refer
to
Section
8.2.3)
and
restart
the
chiller.
If
the
chiller
starts
adjust
the
globe
valve
until
the
recirculation
flow
rate
reaches
the
flow
specified
in
Table
1.
If
the
fault
persists
contact
DTS
Service.
AL*030
Process
Fluid
Press
Hi
User
reset
The
process
outlet
pressure
has
exceeded
its
maximum
threshold
of
240PSI.
There
is
likely
a
problem
with
the
pressure
relief
bypass
valve.
Contact
DTS
Service.
AL*031
Temp
Limit
Shutdown
Auto
reset
Outlet
fluid
temperature
has
exceeded
130°F.
Verify
that
the
plasma
cutter
heat
load
does
not
exceed
the
specifications
defined
in
Table
1.
Hypertherm, Inc. Part Number: 810540
Summary of Contents for Koolant Koolers N-Series
Page 61: ...Appendix B Electrical Schematics PLC 59 PLC Hypertherm Inc Part Number 810540...
Page 62: ...Appendix B Electrical Schematics I O Module 60 I O Module Hypertherm Inc Part Number 810540...
Page 63: ...Appendix B Electrical Schematics Logic 61 Logic Hypertherm Inc Part Number 810540...
Page 73: ...Appendix E Declaration of Conformity 71 Hypertherm Inc Part Number 810540...
Page 74: ...Appendix E Declaration of Conformity 72 Hypertherm Inc Part Number 810540...
Page 75: ...Appendix E Declaration of Conformity 73 Hypertherm Inc Part Number 810540...