Troubleshooting
‐
Alarm
List
46
Alarm
Code
Alarm
Name
Type
Description
Corrective
Action
AL*032
Recirc
Flow
Prb
Err
Auto
reset
The
flow
signal
from
the
flow
meter
in
the
recirculation
circuit
is
reading
open,
short,
or
out
of
range.
Check
the
M12
Eurofast
electrical
connector
on
the
flow
meter
to
ensure
it
is
fully
tightened.
If
the
fault
persists
contact
DTS
Service.
AL*033
Recirc
Temp
Prb
Err
Auto
reset
The
temperature
signal
from
the
flow
meter
in
the
recirculation
circuit
is
reading
open,
short,
or
our
of
range.
Check
the
M12
Eurofast
electrical
connector
on
the
flow
meter
to
ensure
it
is
fully
tightened.
If
the
fault
persists
contact
DTS
Service.
AL*034
Flit
In
Press
Prb
Err
Auto
reset
The
pressure
signal
from
fluid
filter
inlet
pressure
transducer
is
reading
open,
short,
or
out
of
range.
Check
the
M12
Eurofast
electrical
connector
on
the
pressure
transducer
to
ensure
it
is
fully
tightened.
If
the
fault
persists
contact
DTS
Service.
AL*035
Filt
Out
Press
Prb
Err
Auto
reset
The
pressure
signal
from
fluid
filter
outlet
pressure
transducer
is
reading
open,
short,
or
out
of
range.
Check
the
M12
Eurofast
electrical
connector
on
the
pressure
transducer
to
ensure
it
is
fully
tightened.
If
the
fault
persists
contact
DTS
Service.
AL*036
Process
Press
Prb
Err
Auto
reset
The
pressure
signal
from
process
outlet
pressure
transducer
is
reading
open,
short,
or
out
of
range.
Check
the
M12
Eurofast
electrical
connector
on
the
pressure
transducer
to
ensure
it
is
fully
tightened.
If
the
fault
persists
contact
DTS
Service.
AL*037
Process
Flow
Meter
Err
Auto
reset
The
flow
signal
from
the
process
flow
meter
is
reading
open,
short,
or
out
of
range.
Check
the
M12
Eurofast
electrical
connector
on
the
flow
meter
to
ensure
it
is
fully
tightened.
If
the
fault
persists
contact
DTS
Service.
AL*038
Inlet
Temp
Prb
Err
Auto
reset
The
temperature
signal
from
the
process
flow
meter
is
reading
open,
short,
or
out
of
range.
Check
the
M12
Eurofast
electrical
connector
on
the
flow
meter
to
ensure
it
is
fully
tightened.
If
the
fault
persists
contact
DTS
Service.
AL*039
Tank
Level
Sensor
Err
Auto
reset
The
level
signal
from
the
ultrasonic
tank
level
sensor
is
reading
open,
short,
or
out
of
range.
Check
the
M12
Eurofast
electrical
connector
on
the
tank
level
sensor
to
ensure
it
is
fully
tightened.
If
the
fault
persists
contact
DTS
Service.
AL*040
Cond
Temp
Prb
Err
Auto
reset
The
temperature
signal
from
the
condenser
thermistor
is
reading
open,
short,
or
out
of
range.
Check
the
Deutsch
electrical
connector
on
the
thermistor
to
ensure
it
is
fully
inserted
into
the
mating
connector
on
the
wiring
harness.
If
the
fault
persists
contact
DTS
Service.
AL*041
Suction
Temp
Prb
Err
Auto
reset
The
temperature
signal
from
the
suction
thermistor
is
reading
open,
short,
or
out
of
range.
Check
the
Deutsch
electrical
connector
on
the
thermistor
to
ensure
it
is
fully
inserted
into
the
mating
connector
on
the
wiring
harness.
If
the
fault
persists
contact
DTS
Service.
AL*042
Out
Temp
Prb
Err
Auto
reset
The
temperature
signal
from
the
outlet
fluid
thermistor
is
reading
open,
short,
or
out
of
range.
Check
the
Deutsch
electrical
connector
on
the
thermistor
to
ensure
it
is
fully
inserted
into
the
mating
connector
on
the
wiring
harness.
If
the
fault
persists
contact
DTS
Service.
AL*043
Cond
Press
Prb
Err
Auto
reset
The
pressure
signal
from
the
condenser
pressure
transducer
is
reading
open,
short,
or
out
of
range.
Check
the
electrical
connector
on
the
pressure
transducer
to
ensure
it
is
fully
inserted
into
the
mating
connector
on
the
wiring
harness.
If
the
fault
persists
contact
DTS
Service.
AL*044
Suc
Press
Prb
Err
Auto
reset
The
pressure
signal
from
the
condenser
pressure
transducer
is
reading
open,
short,
or
out
of
range.
Check
the
electrical
connector
on
the
pressure
transducer
to
ensure
it
is
fully
inserted
into
the
mating
connector
on
the
wiring
harness.
If
the
fault
persists
contact
DTS
Service.
AL*045
Ambient
Temp
Prb
Err
Auto
reset
The
temperature
signal
from
the
ambient
thermistor
is
reading
open,
short,
or
out
of
range.
Contact
DTS
Service.
Hypertherm, Inc. Part Number: 810540
Summary of Contents for Koolant Koolers N-Series
Page 61: ...Appendix B Electrical Schematics PLC 59 PLC Hypertherm Inc Part Number 810540...
Page 62: ...Appendix B Electrical Schematics I O Module 60 I O Module Hypertherm Inc Part Number 810540...
Page 63: ...Appendix B Electrical Schematics Logic 61 Logic Hypertherm Inc Part Number 810540...
Page 73: ...Appendix E Declaration of Conformity 71 Hypertherm Inc Part Number 810540...
Page 74: ...Appendix E Declaration of Conformity 72 Hypertherm Inc Part Number 810540...
Page 75: ...Appendix E Declaration of Conformity 73 Hypertherm Inc Part Number 810540...