Operation
‐
Shutdown
27
7.2.1.4
Recirculation Pump Check
From
the
chiller
controller
home
screen
press
and/or
to
highlight
the
MONITORING
selection.
Press
to
access
the
MONITORING
menu
and
press
until
the
“Recirculation
Circuit”
monitoring
screen
appears.
Check
the
recirculation
pump
“Flow
Rate”
to
make
sure
it
exceeds
13.8gpm
(52.2lpm)
at
50Hz
or
16.2gpm
(61.3lpm)
at
60Hz.
If
the
recirculation
pump
flow
rate
is
low,
the
flow
rate
can
be
increased
by
opening
the
globe
valve
at
the
recirculation
pump
outlet.
7.2.1.5
Temperature Check
From
the
chiller
controller
home
screen
press
and/or
to
highlight
the
MONITORING
selection.
Press
to
access
the
Monitoring
menu.
The
first
screen
will
be
the
Process
Temperature
Monitoring
screen.
Check
the
“Tout”
on
this
screen.
On
initial
startup
the
outlet
temperature
may
be
below
the
setpoint.
To
increase
the
temperature
quickly
the
chiller
will
turn
on
the
tank
heater
to
warm
up
the
coolant.
Within
a
few
minutes
the
outlet
temperature
should
settle
in
close
to
the
setpoint.
7.2.2
Remote
Mode
Once
the
chiller
temperature
is
in
the
desired
range,
the
chiller
is
ready
to
be
controlled
remotely
by
the
plasma
cutting
system.
To
enable
Remote
Mode,
turn
the
Local/Off/Remote
Switch
below
the
controller
to
the
position.
There
should
now
be
a
“Unit
on
in
Remote
Mode”
message
on
the
home
screen.
The
chiller
will
now
be
running
in
Standby
Mode
awaiting
the
Remote
Start
signal
from
the
plasma
cutting
system.
While
in
Standby
Mode
the
refrigeration
system
will
not
run,
but
the
chiller
will
start
the
pumps
and
heater
as
needed
to
keep
the
water
warm.
NOTICE
While
waiting
for
the
Remote
Start
signal,
the
chiller
water
temperature
may
exceed
the
setpoints
if
the
ambient
temperature
is
high.
As
soon
as
the
chiller
receives
the
Remote
Start
signal,
the
refrigeration
system
will
start
and
the
water
temperatures
will
drop
to
the
setpoints.
7.3
Shutdown
For
normal
shutdown,
turn
the
Local/Off/Remote
Switch
below
the
controller
to
the
“O”
position.
The
chiller
controller
will
begin
the
normal
shutdown
sequence
and
display
a
“Shutdown
in
Progress”
status
message.
The
normal
shutdown
sequence
typically
takes
2
‐
5
minutes.
During
this
time
the
controller
closes
the
liquid
line
solenoid
in
the
refrigeration
system
and
pumps
the
refrigerant
into
the
coil,
so
there
is
no
risk
of
slugging
liquid
refrigerant
through
the
compressor
on
the
next
startup.
It
also
turns
off
the
tank
heater
while
the
recirculation
pump
continues
to
run
to
dissipate
any
residual
heat
in
the
heater
element.
Once
the
shutdown
sequence
is
complete,
the
chiller
controller
will
display
a
“UNIT
OFF”
status
message.
CAUTION
Shutting
off
the
chiller
using
the
Main
Disconnect
Handle
will
bypass
the
normal
shutdown
sequence
and
should
only
be
used
in
emergency
situations.
Repeated
shutdown
using
the
main
disconnect
handle
will
cause
damage
to
the
compressor
system
and
void
the
chiller
warranty.
It
can
also
cause
overheating
of
the
inline
heater
and
trip
the
heater
limit
switch.
Hypertherm, Inc. Part Number: 810540
Summary of Contents for Koolant Koolers N-Series
Page 61: ...Appendix B Electrical Schematics PLC 59 PLC Hypertherm Inc Part Number 810540...
Page 62: ...Appendix B Electrical Schematics I O Module 60 I O Module Hypertherm Inc Part Number 810540...
Page 63: ...Appendix B Electrical Schematics Logic 61 Logic Hypertherm Inc Part Number 810540...
Page 73: ...Appendix E Declaration of Conformity 71 Hypertherm Inc Part Number 810540...
Page 74: ...Appendix E Declaration of Conformity 72 Hypertherm Inc Part Number 810540...
Page 75: ...Appendix E Declaration of Conformity 73 Hypertherm Inc Part Number 810540...