Water leaks from
steam cylinder
upper part
•
Hose clamps on steam and/or conden-
sate hose not tightened
•
Tighten clamps
•
Steam hose adapter not properly fit or
O-ring not replaced
•
Replace O-ring (if required) and
ensure proper adapter installa-
tion
No steam produc-
tion despite the
steam humidifier
being switched
on. Display not
illuminated.
•
•
•
Defective F1 and/or F2 fuses (1.6 A each)
Failure of the control voltage (ext. circuit
breaker has tripped or is defective)
Device load circuit breaker has tripped
•
•
•
Check micro fuses and replace,
if required
Replace breaker and investi-
gate possible causes
Switch on breaker. If problem
persists, check for reason
No steam produc-
tion. Voltage
across electrodes
exist, but no wa-
ter is fed into the
cylinder
•
Water supply not opened or solenoid
valve electrically not driven
•
Open water supply (s. also
Fill-
ing
fault messages 030)
No steam produc-
tion despite the
steam generator
being switched
on and an illumi-
nated display
•
•
•
The interlock (safety) system is open
The humidity set value has been reached.
The control receives no demand for
steam production.
A fault has occurred
•
•
•
Close interlock (safety) system
Check humidity set value and
plausibility of actual humidity
value
Check unit status
Blow-down pump
works but not wa-
ter is drained
•
Steam cylinder and/or drainage system
blocked
•
Clean cylinder base and/or
drainage system, respectively
Cylinder is fully
drained after par-
tial blow-down
despite pump
beeing switched
off
•
Vent pipe is blocked
•
Clean venting bore or replace
vent pipe adapter
Problem
Possible cause for faulty situation
Counter measure