Submenu „Functions“ (Group 5)
Submenu „Settings“ (Group 6)
Par.
Denomination
Setting options
Code
5-1
Switch stand-by heating
0=off, 1=on
Fs = 0
10
5-2
Interval stand-by heating [min]
1...999
Fs = device dependant
10
5-3
Stand-by heating [s]
1...999
Fs = device dependant
10
5-4
Basic relay
0 = collective fault
1 = stand-by
2 = no demand
3 = humidifying
5 = remote off
30 = filling off
31 = filling on
37 = HyCool
60 = Blow-down off
61 = Blow-down on
62 = Partial blow-down
63 = Full blow-down
66 = max. level
67 = Stand-by blow-down
68 = Dead leg flushing
69 = Start-up blow-down
270 = Collectice Service
Fs = 0
5-5
Relay_K20
same as for basic relay
Fs = 270
10
5-6
Modbus address
0..255
Fs = 1
10
5-7
Relay_K21
same as for basic relay
Fs = 270
Par.
Denomination
Setting options
Code
6-1
Buzzer
0=off, 1=on
Fs = 0
10
6-2
Time-Out (return to standard
display) [min]
0 ... 60
Fs = 2
10
6-3
Activate imperial units
0 = SI units
1 = imperial units
Fs = 0
10