Page 15
Mounting principle
For wall mounting drill measures, please
consult the table above (measure A). In case
of no suitable wall available for mounting the
unit, it is recommended that installation is
made on brackets firmly anchored in the
floor.
»
mark the holes for the upper
suspension brackets
screws.
»
drill holes and dowel.
»
screw in the supplied mounting
screws; let the screws protrude
approx. 12 mm
/
.5 inch from wall.
»
ensure firm fixation and load-carry-
ing capacity of the mounted screws!
»
hook in the unit and ensure safe
suspension.
»
mark the holes for the lower suspen-
sion brackets screws.
»
remove the unit.
»
drill holes and dowel.
»
hook in the unit and mount the lower
screws firmly.
•
To function properly, the steam humidi-
fier must hang level and plumb.
•
When choosing the installation loca-
tion, consider the necessary distance
between the unit and existing designa-
ted paths. This should be at least 60
cm.
•
The mounting wall must be made of a
temperature-resistant material, as the
enclosure can heat up to 70°C.
Device connections:
device rear
suspension brackets
Please note
steam outlet
water inlet
cable entries
waste water connection