Page 56
11.6 Tabular representation of
reading value list and pro-
vider level submenus
For a detailed description, pls. refer to the
respective sections within this chapter.
11.6.1 The reading value list
From normal operation, the user may access
the reading value index „r01“ (Status) by
pressing any key.
By scrolling using the keys the reading
and setting values indicated in the table
below may be addressed. To output the value
content, the SET key must be pressed first.
11.6.2 Provider level submenus and
relating parameters
Detailed parameter descriptions may be
found in the section „Detailed parameter
description“ further down in this chapter. The
„Setting options“ column indicates the preset-
tings available or the range of values to be
chosen from. „Fs“ stands for „Factory set-
ting“.
Submenu „Control“ (Group1)
*) Fs = Factory setting
<
<
„ / “
Reading
value
index
Description
r01
Status
r02
Fault
r03
Actual steam output [kg/h]
r04
Actual steam outpt [lb/h] (only
when imperial units were
selected)
r05
Actual current [A]
(only for electrode steam humidifiers)
r06
Filling level [mm]
(only for heater steam humidifiers)
r07
Internal demand [%]
r08
External demand [%]
r09
Power limitation [%]
r10
Set value r.h. [%] (only when PI
controller was selected)
r11
Actual value r.h. [%] (only when
PI controller was selected)
r12
External signal [%]
r13
V-Signal
r14
mA-Signal
r15
Ω
-Signal
P00
Code level („0“, „10“)
PAr
Parameter group selection
Par.
Denomination
Setting options
Code
1-1
Steam output max.
[%]
25 ... 100
Fs*) = 100
10
1-2
Control signal
0= not valid
1= ext. controller, 0 ... 10 V
2= ext. controller, 0 ... 20 mA
3= ext. controller, 0..140
Ω
4= PI controller, 0 ... 10 V
5= PI controller, 4 ... 20 mA
6= PI controller, 0 ...140
Ω
7= 1-step
8= Modbus
Fs = 1
10
1-3
Correction input stages
[%]
-5.0 ... +5.0
Fs = 0
10
1-4
Filter input stage
0=light, 1=strong
Fs = 0