![Hygood FM-200 Installation Manual Download Page 98](http://html1.mh-extra.com/html/hygood/fm-200/fm-200_installation-manual_2192834098.webp)
Consolidated Report
Predicted Concentration: 6.411%
Maximum Expected Agent Concentration: 6.411% (At 20.0 C)
Minimum
Agent
Required
Nozzle
Adjusted
Agent
Required
Predicted
Agent
Delivered
Nozzle
Pressure
(Average)
E2-N1
67.9 kg
68.2 kg
68.5 kg
6.887 bar
E2-N2
67.9 kg
68.2 kg
68.5 kg
6.887 bar
E2-N3
67.8 kg
68.0 kg
67.5 kg
6.069 bar
E2-N4
67.8 kg
68.0 kg
67.5 kg
6.069 bar
Standard Isometric View
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
Page:
9
10
of
Calculation Date/Time: Sunday, June 29, 2008, 12:24:17 PM
9
APPENDIX B - HUGHES PROGRAM PRINTOUT
FM-200® (UL/FM)
14A-07H
02
2010-03