Consolidated Report
Elevation: 0 m (relative to sea level)
Atmospheric Correction Factor: 1
Enclosure Information
Enclosure Number: 2
Name: Computer Room
Enclosure Temperature...
Minimum: 20.0 C
Maximum: 20.0 C
Maximum Concentration: 6.422 %
Design Concentration...
Adjusted: 6.422 %
Minimum:
Minimum Agent Required:
Width:
Length:
Height:
Volume:
Non-permeable:
Total Volume:
Adjusted Agent Required:
Number of Nozzles:
6.400 %
271.4 kg
12.00 m
16.00 m
2.83 m
543.36 cubic m
0.00 cubic m
543.36 cubic m
272.4 kg
4
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
Page:
3
10
of
Calculation Date/Time: Sunday, June 29, 2008, 12:24:17 PM
Consolidated Report
Agent Information
Agent: FM-200 / Propellant N2
(FM-200 is a Trademark of DuPont.)
Adjusted Agent Required: 333.0 kg
Container Name: 180L DOT Container Assy
Container Part Number: 304.205.021
Number of Main Containers:
Number of Reserve Containers:
3
0
Manifold: 3 Port 80mm End Manifold Assy (BSP) -
52-180L
Horizontal
Pipe Take Off Direction:
Agent Per Container: 111.0 kg
Fill Density: 0.617 kg / l
Container Empty Weight: 105.8 kg
Weight, All Cont Agent: 650.4 kg
Floor Area Per Container: 0.13 square m
Floor Loading Per Container: 1681 kg /square m
Pipe Network
Part 1 - Pipe
Description
Start End
Type
Diameter
Length
Elevation
Pipe
Main Cyl. X 3
0
1
50 mm
1.63 m
1.63 m
Manifold X 3
1
2
US40B
TS
50 mm
0.74 m
0.62 m
Manifold X 1
2
3
UK80B
WS
80 mm
1.17 m
0.00 m
Pipe
3
4
UK80G
TS
80 mm
0.45 m
0.45 m
Pipe
4
5
UK80G
TS
80 mm
0.45 m
0.00 m
Pipe
5
6
UK80G
TS
80 mm
2.25 m
0.00 m
Pipe
6
7
UK80G
TS
80 mm
3.75 m
0.00 m
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
Page:
4
10
of
Calculation Date/Time: Sunday, June 29, 2008, 12:24:17 PM
93
© 2010 Macron Safety Systems (UK) Limited
APPENDIX B - HUGHES PROGRAM PRINTOUT
EQUIPMENT:
FM-200® (UL/FM)
PUBLICATION:
14A-07H
ISSUE No.
02
DATE:
2010-03