Ancillary Equipment
Discharge Pressure Switch
Single Container Systems
On single container installations the pressure switch should
be located close to the valve assembly and connected with
a pilot hose from the pressure port outlet on the valve to
the connector on the pressure switch (see Figure 63)��
Figure 3 - Discharge Pressure Switch Installation (Single
Container System)
Multiple Container Systems
On multi-container installations the pressure switch should
be located close to the last slave container and connected
by pilot hose to the tee connector on the pneumatic actuator
(see Figure 64)��
Figure 4 - Discharge Pressure Switch Installation (Multiple
Container System)
3
© 2010 Macron Safety Systems (UK) Limited
SECTION 5 - INSTALLATION
EQUIPMENT:
FM-200® (UL/FM)
PUBLICATION:
14A-07H
ISSUE No.
02
DATE:
2010-03