SECTION 3 - SYSTEM DESIGN
HYGOOD
34
FM-200
®
Installation Guide/11100/02.08.05/Issue 3.3
Maximum Limits in Pipe Work.
Figure 25a -
Figure 25b -
Figure 25c -
If nozzles are only located
above
the
container outlet, then the maximum elevation difference
between the container outlet and the furthest horizontal
pipe run or discharge nozzle (whichever is furthest) shall
not exceed 9��1m (30 ft)�� See figure 25a��
If nozzles are only located
below
the
container outlet, then the maximum elevation difference
between the container outlet and the furthest horizontal
pipe run or discharge nozzle (whichever is furthest) shall
not exceed 9��1m (30 ft)�� See Figure 25b��
If nozzles are located both
above and
below
the container outlet, then the maximum distance
between the furthest horizontal pipe runs, or discharge
nozzles (whichever is further) shall not exceed 9��1m (30
ft)�� See figure 25c��
Note
: If a system design violates
these limits, contact Macron Safety
Systems to determine what action
has to be taken��
Examples:
SECTION 3 - SYSTEM DESIGN
HYGOOD
34
FM-200
®
Installation Guide/11100/02.08.05/Issue 3.3
Maximum Limits in Pipe Work.
Figure 25a -
Figure 25b -
Figure 25c -
If nozzles are only located
above
the
container outlet, then the maximum elevation difference
between the container outlet and the furthest horizontal
pipe run or discharge nozzle (whichever is furthest) shall
not exceed 9��1m (30 ft)�� See figure 25a��
If nozzles are only located
below
the
container outlet, then the maximum elevation difference
between the container outlet and the furthest horizontal
pipe run or discharge nozzle (whichever is furthest) shall
not exceed 9��1m (30 ft)�� See Figure 25b��
If nozzles are located both
above and
below
the container outlet, then the maximum distance
between the furthest horizontal pipe runs, or discharge
nozzles (whichever is further) shall not exceed 9��1m (30
ft)�� See figure 25c��
Note
: If a system design violates
these limits, contact Macron Safety
Systems to determine what action
has to be taken��
Examples:
SECTION 3 - SYSTEM DESIGN
HYGOOD
34
FM-200
®
Installation Guide/11100/02.08.05/Issue 3.3
Maximum Limits in Pipe Work.
Figure 25a -
Figure 25b -
Figure 25c -
If nozzles are only located
above
the
container outlet, then the maximum elevation difference
between the container outlet and the furthest horizontal
pipe run or discharge nozzle (whichever is furthest) shall
not exceed 9��1m (30 ft)�� See figure 25a��
If nozzles are only located
below
the
container outlet, then the maximum elevation difference
between the container outlet and the furthest horizontal
pipe run or discharge nozzle (whichever is furthest) shall
not exceed 9��1m (30 ft)�� See Figure 25b��
If nozzles are located both
above and
below
the container outlet, then the maximum distance
between the furthest horizontal pipe runs, or discharge
nozzles (whichever is further) shall not exceed 9��1m (30
ft)�� See figure 25c��
Note
: If a system design violates
these limits, contact Macron Safety
Systems to determine what action
has to be taken��
Examples:
Maximum Limits (Elevation) in Pipe Work.
Examples:
If nozzles are only located above the container outlet, then the maximum elevation difference between the container
outlet and the furthest horizontal pipe run or discharge nozzle (whichever is furthest) shall not exceed 9��1 m (30 ft)�� See
Figure 35��
If nozzles are only located below the container outlet, then the maximum elevation difference between the container
outlet and the furthest horizontal pipe run or discharge nozzle (whichever is furthest) shall not exceed 9��1 m (30 ft)�� See
Figure 36��
If nozzles are located both above and below the container outlet, then the maximum distance between the furthest
horizontal pipe runs, or discharge nozzles (whichever is further) shall not exceed 9��1 m (30 ft)�� See Figure 37��
Figure 3 - Nozzles Located Above the Container Outlet
Figure 3 - Nozzles Located Below the Container Outlet
Figure 37 - Nozzles Located Above and Below the Container Outlet
Note: If a system design violates these
limits, contact the technical support centre
to determine what action has to be taken.
9.1 m (30 ft)
9.1 m (30 ft)
4. m (1 ft)
9.1 m (30 ft)
9.1 m (30 ft)
4. m (1 ft)
9.1 m (30 ft)
41
© 2010 Macron Safety Systems (UK) Limited
SECTION 3 - SYSTEM DESIGN
EQUIPMENT:
FM-200® (UL/FM)
PUBLICATION:
14A-07H
ISSUE No.
02
DATE:
2010-03