4.-.2 mm
(0.19-0.20 in)
WITH NUT
AGAINST BODY
Figure 4 - Actuator Non-Fire Position
Figure - Electrical Actuator Location
If no other actuators are to be installed ensure that the
protective cap on the actuator is retained in position��
Actuation Installation
The method of actuation depends on the system
configuration and any specific contract requirements and
can be broken down as follows:
Single Container Actuation
Multiple Container Actuation
Single Container Actuation
Removable Electrical Actuator
The removable electrical actuator is fitted to the top of the
valve assembly as follows:
Check the actuator mechanism to ensure that it is in
the non-fired position by fully screwing in the reset
tool, i��e�� pin retracted (see Figure 54)��
Remove the actuator cap from the top of the valve
assembly (see Figure 46)��
Carefully screw the actuator to the valve assembly
(see Figure 55)��
Note: The actuator must be hand tight only.
•
•
•
•
•