Now choose your Call out mode, this can be
either “Freq” for a call made at a regular
frequency throughout the day or “Time” to
specify up to 8 individual times during the day.
Enter either the frequency (e.g. 00:05 minutes) or the time for
the call in the box.
viii.
Alarms
– The Multilog LX 2 has a comprehensive alarm system
that you can configure to send out Alarm messages when
certain defined conditions are breached.
When an alarm condition is triggered a new call frequency can be specified to
allow the observer to gain more up-to-date data during an event.
Minimum
Night
Flow
is
measured between Midnight
and the time specified here.
Choose your flow units
If
you
want
SMS
alarm
messages to be sent, tick this
box and enter a phone number
There are 8 possible different
alarm conditions that can be
configured, select each one
from the tabs.
Choose the main alarm channel
and then the difference channel
if making a comparison.
Set your persistence or trigger
point, e.g. 3 occurrences out of
5 incidents triggers the alarm
Choose your type of alarm from
the list:-
Lower
or
Upper
Limit breach
Enter the alarm threshold
Minimum Night Flow (
MNF
) not met
Rate Of Change (
ROC
) faster than x per minute
Difference (
Dif
) between channels greater or less than limit
Either
In
or
Out
of
Band
set by Upper & Lower levels
Note on Hysteresis
: When an alarm is triggered, if the value is
set to zero then immediately the threshold is re-crossed then
another clear message will be sent. If there is a period when the
alarm threshold is borderline, this can result in numerous
messages for the same event. By specifying a value in the
Hysteresis box, you can provide a window that allows the
threshold to be repeatedly crossed without sending repeated
messages. e.g with an Upper limit of 5 and a hysteresis of 1, the
alarm will trigger at 5, but the clear message will not be sent
until the value drops to below 4.
Enter the alarm
clear Hysteresis