UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)
3 Installation
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
69
3.2.3.6 Installing a Battery Grounding Failure Detector
Procedure
Step 1
Install a battery grounding failure detector.
For details, see the
UPS Battery Grounding Failure Detector User Manual
shows the position of the battery grounding failure detector on the UPS.
Figure 3-36
Position of the battery grounding failure detector on the UPS
(1) Battery grounding failure detector
After battery installation, check that the battery voltage is 10.5–13.5 V and the battery voltage difference
is less than or equal to 5%. If the conditions are not met, charge or replace the batteries.
----End