UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)
3 Installation
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
95
No.
Item
Acceptance Criteria
voltage of a battery (2 V or 12 V).
13
Operating environment
The inside and outside of the cabinet, and
other operating components, are free from
conductive dust.
14
Copper busbar short circuit
Copper busbars are confirmed as being
open-circuited using a multimeter, or an
insulation resistance tester.
1.
In the scenarios where holes are drilled for routing cables or covers are removed for routing cables,
after routing cables and checking cable connections, use sealing putty to fill in the gap between the
cables and the cabinet.
2.
After verifying the installation, reinstall all the covers.
3.
Do not remove the dustproof cover before power-on to prevent dust inside the UPS.