UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)
8 Technical Specifications
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
183
Item
400 kVA
(line voltage)
Frequency
In normal mode, the mains frequency is synchronous
with the bypass input frequency. The frequency is 50
Hz or 60 Hz (tolerance ±0.25%) (local frequency of
the inverter).
Total harmonic distortion of
output voltage (THDv)
< 1% (full linear load)
< 4% (full non-linear load)
Output PF
0.9
Transfer time
0 ms
Output voltage unbalance
Voltage unbalance: ±3%; phase unbalance: ±2°
Overload capability
Inverter overload capability:
105% < load ≤ 110%: transfer to bypass mode after
60 min
110% < load ≤ 125%: transfer to bypass mode after
10 min
125% < load ≤ 150%: transfer to bypass mode after
1 min
Bypass overload capability:
105% < load ≤ 110%, 60 min in bypass mode
110% < load ≤ 125%: 10 min in bypass mode
125% < load ≤ 150%: 1 min in bypass mode
Load = 1000%: 100 ms in bypass mode
8.8 System Electrical Specifications
System Specifications
400 kVA
Number of the parallel UPSs
≤ 4
Power supply reliability
The auxiliary power supplies, centralized controllers,
and parallel signals use a redundancy design.
ECO
Supported