STS-6000K-H1 Smart Transformer Station (Vietnam,
Duc Long Gai Lai)
Installation Guide
7 Connecting Cables
Issue 02 (2020-02-21)
Copyright © Huawei Technologies Co., Ltd.
43
Table 7-1
Cables
No.
Cable
Type
Cross-sectional
Area
Outer Diameter
Source
1
PE cable
Single-core outdoor
copper cable and M12
OT/DT terminals
50–240 mm
2
10–32 mm
Prepared by
the customer
2
AC input
power cable
a
Single-core or three-core
outdoor
copper/copper-clad
aluminum/aluminum
alloy cable and M12
OT/DT terminals
50–240 mm
2
16–72 mm
Prepared by
the customer
3
UPS cable
bundle
N/A
N/A
N/A
Delivered
with the
product
4
SACU cable
bundle
N/A
N/A
N/A
Delivered
with the
product
5
(Optional)
Tracking
system power
cable
Three-core or four-core
outdoor copper cable
2.5–16 mm
2
10–32 mm
Prepared by
the customer
6
(Optional)
Site auxiliary
power supply
cable
Two-core or three-core
outdoor copper cable
2.5–10 mm
2
6–20 mm
Prepared by
the customer
7
Cabinet G1
cable
Single-core or three-core
outdoor
copper/copper-clad
aluminum/aluminum
alloy cable and separable
shielded cable
connectors
70–300 mm
2
Single-core: 30–52
mm
Three-core: 30–95
mm
Prepared by
the customer
8
Cabinet G3
cable
Prepared by
the customer
Note a: The AC input power cable can connect to a 300 mm
2
or 400 mm
2
single-core cable. The restrictions are
as follows:
Outer diameter of a single-core cable ≤ 35 mm
Dimensions of the wiring terminal: width ≤ 43 mm; length ≤ 136.5 mm; outer diameter of the crimping tube
≤ 37 mm
7.2 Connecting a PE Cable for the STS
Grounding Requirements
The grounding should comply with the local electrical safety regulations.