PowerCube 5000
User Manual (SmartLi 100Ah)
2 Products
Issue 02 (2020-03-17)
Copyright © Huawei Technologies Co., Ltd.
19
Table 2-1
Indicator description
Definition Color
Status
Meaning
Power
indicator
Green
Off
The HSU has no input power.
On
The HSU output is normal.
Blinkin
g
Frequency 0.5 Hz:
1.
The HSU works in bypass mode (on for 1s and off
for 1s)
2.
The HSU has no AC output (on for 0.125s and off
for 1.875s)
Frequency 4 Hz:
1.
The HSU is being configured.
2.
The HSU is being loaded online.
Alarm
indicator
Yellow
Off
No protection is triggered by external conditions.
Blinkin
g
Frequency 0.5 Hz (on for 1s and off for 1s)
There is a PFC soft-start failure alarm.
DC bus pre-charging has failed.
On
Protection is triggered by external conditions or
temporary malfunction is caused by internal factors.
Fault
indicator
Red
Off
There is no internal fault or EPO.
On
Protection, protective lockout, EPO, or module
unreadiness is caused by internal component faults.
Table 2-2
Specifications
Parameter
Description
Dimensions (H x W x D)
130 mm x 442 mm x 620 mm
Weight
< 34 kg
Operating temperature
–25°C to +55°C
Rated output capacity
33 kVA
AC output voltage
380 V AC/400 V AC/415 V AC
Battery voltage
336–800 V DC
PV input voltage
200–980 V DC
PV input power
Max.: 33 kW
2.3.2 Bypass Module (BPS)
The BPS supplies power when the power from the DG is in use.