5 Power-on Commissioning
Issue 02 (2020-03-17)
Copyright © Huawei Technologies Co., Ltd.
103
Table 5-5
Settings Wizard
Item
Parameter
Setting
Language
N/A
Select a desired language.
Time
N/A
Set to the local time and date.
System
Param.
Battery cabinet
quantity
Set this parameter as required.
Modules per rack
Set this parameter based on the number of battery
strings in the lithium battery cabinet.
Module battery LVD
voltage
If the voltage of a single battery module is lower
than the value of this parameter, the battery module
is automatically powered off. Set this parameter
based on site requirements.
EPO enable
To enable the EPO function, set this parameter to
Enable.
Fire control enable
If this parameter is set to
Enable
, an alarm is
reported after the fire extinguishing action is
triggered.
Network
Param.
IP address allocation
If the MDU is directly connected to a computer,
the IP address can only be allocated manually.
The IP addresses of the MDU and network
management system must be on the same
network segment, and must be different.
If the MDU is connected to a computer through
a LAN switch or router with the DHCP
function, the IP address can be allocated
manually or automatically. Manual allocation is
used by default.
IP address
Set this parameter according to the address
information provided by the network administrator.
The IP address of the lithium battery cabinet must
be the same as the lithium battery cabinet IP
address set in the ICC cabinet.
Subnet mask
Default gateway
----End
5.5 Powering On Loads
Procedure
Step 1
Turn the output disconnector of the isolation transformer to ON.
Step 2
Turn the AC output circuit breaker in the ICC cabinet to ON.
Step 3
Enable the system output.