PowerCube 5000
User Manual (SmartLi 100Ah)
2 Products
Issue 02 (2020-03-17)
Copyright © Huawei Technologies Co., Ltd.
22
2.3.3.1 SMU02S
Panel
Figure 2-11
SMU02S panel
(1) SD card slot
(2) Running indicator
(3) Minor alarm indicator
(4) Major alarm indicator
(5) Buttons
(6) USB port
(7) RS485/RS232 port
(8) Fast Ethernet (FE) port
(9) CAN communications port
(10) LCD
Indicators
Table 2-5
Indicator description
Name
Color
Status
Description
Running
indicator
Green
Off
The SMU is faulty or has no DC input.
Blinking
slowly (0.5
Hz)
The SMU is running properly and
communicating with the host properly.
Blinking fast
(4 Hz)
The SMU is running properly but fails to
communicate with the host properly.
Minor alarm
indicator
Yellow
Off
No minor or warning alarm is generated.
Steady on
A minor or warning alarm is generated.
Major alarm
indicator
Red
Off
No critical or major alarm is generated.
Steady on
A critical or major alarm is generated.