Item
Technical Specifications
Humidity range
5%–90% RH
Storage
temperature
–40°C to +70°C
Storage humidity
5%–95% RH (non-condensing)
Inlet water
temperature range
of chilled water
10°C to 37°C
Highest operating
temperature of the
refrigerant side
125°C
Highest operating
temperature of the
cooling water
60°C
Water flow rate
9.5 m
3
/h
Water-side pressure
bearing
1.2 MPa
Refrigerant-side
pressure bearing
4.35 MPa
IP rating
IP21
Altitude
0–4000 m (derated when the altitude is greater than 1000
m)
Environment
Enclosed indoor environment in which the temperature
and humidity can be controlled within the ranges of 4°C
to 45°C and 5% RH to 90% RH respectively. If the indoor
installation position is ventilated, it should be more than
3.7 km away from the sea or pollution sources (such as
salt lakes, chemical plants, mineral plants, thermal power
plants, and coal mines).
Dimensions (H x W
x D) (mm)
530 x 1510 x 262
Net weight
63 kg
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
3 Technical Specifications
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
32