Symptom
Possible Cause
Solution
The
compressor
switch trips
abnormally
.
The switch is faulty.
Replace the compressor switch.
The electric
heating
belt of the
crankcase
does not
heat.
1. The electric heating belt of
the crankcase is
disconnected abnormally.
2. The fuse has blown.
3. The electric heating belt of
the crankcase is short-
circuited abnormally, and
the fuse has blown.
1. Replace the electric heating
belt of the crankcase.
2. Replace the fuse.
3. Replace the electric heating
belt of the crankcase and the
fuse.
The electric
heating
belt of the
crankcase
does not
stop
heating.
The relay contacts of the
electric heating belt of the
crankcase are short-circuited.
Replace the electric heating belt
of the crankcase relay.
NO TE
If the fault persists, contact Huawei technical support.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
10 Troubleshooting
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.