Alarm
ID
Alarm Name
Alar
m
Seve
rity
Possible Cause
Solution
A038-0
1
Compressor
Liquid pipe
temp sensor
fault
MAJ
OR
1. The cables to
the liquid pipe
temperature
sensor are loose or
damaged.
2. The liquid pipe
temperature
sensor is faulty.
1. Check the cables to
the liquid pipe
temperature sensor.
2. Maintain or replace
the liquid pipe
temperature sensor.
A040-0
1
PSU 1 power
supply
abnormal
MAJ
OR
The input power
cables of the PSU
are loose or
damaged.
1. Check the input
power cables of the
PSU.
A040-0
1
PSU 2 power
supply
abnormal
MAJ
OR
The input power
cables of the PSU
are loose or
damaged.
1. Check the input
power cables of the
PSU.
A042-0
1
Remote
shutdown
alarm
CRITI
CAL
1. The remote
shutdown dry
contact is
triggered.
2. The cables to
the remote
shutdown dry
contact are loose
or damaged.
1. Check the status of
the remote shutdown
dry contact.
2. Check the cables to
the remote shutdown
dry contact.
A044-0
1
Smoke sensor
alarm
CRITI
CAL
1. Smoke is
generated in the
equipment room.
2. The cables to
the smoke sensor
are loose or
damaged.
3. The smoke
sensor is faulty.
1. Expel smoke from
the equipment room
and reset the smoke
sensor.
2. Check the cables to
the smoke sensor.
3. Maintain or replace
the smoke sensor.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
9 Alarm Reference
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
192