12.1 How Do I Issue a Start/Shutdown Command?
You can use the start/shutdown signal over the smart cooling product LCD, ECC
WebUI, or NetEco WebUI, or hardware port to start or shut down the smart
cooling product.
Scenario
Operation
Start/Shutdown
Signal Status -
LCD/ECC/NetEco
WebUI
Start/Shutdown
Signal Status -
Hardware Port
If the equipment
is started, issue a
shutdown
command to shut
down the
equipment.
Method 1: Set the start/
shutdown signal to
shutdown on the smart
cooling product LCD, ECC
WebUI, or NetEco WebUI.
Shutdown
Start
Method 2: Connect the
remote start/shutdown dry
contacts of the hardware
port.
Start
Shutdown
If the equipment
is shut down,
issue a start
command to
start the
equipment.
1. Check that the remote
start/shutdown signal
status of the hardware
port is start.
2. Set the start/shutdown
control signal to start on
the smart cooling
product LCD, ECC
WebUI, or NetEco
WebUI.
Start
Start
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual