Paramete
r
Description
Setting Rule
Default
Value
Cold aisle
temperatu
re and
humidity
sharing
This function can be
enabled only when at least
one smart cooling product
in the group is equipped
with cold aisle T/H sensors.
If this function is enabled,
the master unit in the
teamwork group collects
the cold aisle temperature
and humidity values from
all units equipped with cold
aisle sensors, and
synchronizes the
temperature and humidity
values after logical
calculation to all units.
NOTE
After this function is enabled,
the master unit synchronizes
the temperature and humidity
control type and setpoints to
all slave units.
This parameter can be
enabled when there
are at least one smart
cooling products in
the group are
configured with cold
aisle T/H sensors.
Disable
Hot aisle
temperatu
re and
humidity
sharing
This function can be
enabled only when at least
one smart cooling product
in the group is equipped
with hot aisle T/H sensors.
If this function is enabled,
the master unit in the
teamwork group collects
the hot aisle temperature
and humidity values from
all units equipped with hot
aisle sensors, and
synchronizes the
temperature and humidity
values after logical
calculation to all units.
NOTE
After this function is enabled,
the master unit synchronizes
the temperature and humidity
control type and setpoints to
all slave units.
This parameter can be
enabled when there
are at least one smart
cooling products in
the group are
configured with hot
aisle T/H sensors.
Disable
Step 3 Complete the teamwork settings for all the smart cooling products by performing
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
6 Power-On Commissioning
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
147