System address: The address (configurable range: 1-32) of each smart cooling
product in the same group must be unique. The smart cooling product with
the smallest unit address is the master unit, which collects, processes, and
delivers group data.
Context
The parameters in this section are for reference only. Set practical parameter
values as required.
Procedure
Step 1 On the home screen, tap
> Teamwork Settings to enter the Teamwork
Settings screen, as shown in
.
Figure 6-11 Teamwork settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., System address, Enable teamwork CAN resistor,
Teamwork function and Networking mode can be set on slave smart cooling
products. Other parameters of the slave units will be modified by the master unit
synchronously.
describes how to set the parameters.
Table 6-7 Teamwork settings
Paramete
r
Description
Setting Rule
Default
Value
Teamwork
group No.
The number of the
teamwork group. This
parameter should be the
same for all units in the
same teamwork group.
Set the assigned
teamwork control
number.
1
System
address
The addresses of units in
the same teamwork group
cannot be the same.
Set the planned unit
address.
NA