Page 12
Copyright © Huawei Technologies Co., Ltd. 2020
1.2 Routine Inspection-Onsite Inspection
Equipment room environment inspection covers temperature, humidity,
and power supply.
No.
Item
Result
Reference
1
Operating
temperature
10
°
C to 35
°
C (41
°
F to 95
°
F)
2
Storage
temperature
–40
°
C to +65
°
C (
–40
°
F to +149
°
F)
3
Maximum
fluctuation rate
15
°
C/h (59
°
F/h)
4
Operating humidity
8% to 90% RH (non-condensing)
5
Storage humidity
5% to 95% RH (non-condensing)
6
Operating altitude
≤ 3000 m (9842 ft.)
7
PSUs
AC input: 100 V to 240 V AC at 50 Hz or 60 Hz
DC input:
–48 V DC (nominal voltage), –38.4 V to –
57.6 V DC (voltage range)