54
Function 4
Warm Weather Shutoff
Description: Warm Weather Shutoff disables the heating module and the Total System Control will then
optimize for domestic hot water only. Warm Weather Shutoff will occur if the programmed outdoor
temperature is exceeded by the current outdoor sensor temperature. Factory default 68
o
F (Range 41
o
F to
122
o
F).
Function 5
Min Outdoor Temp
Description: Allows the user to set the minimum outdoor design temperature for the system. Factory
default 5
o
F (Range -49
o
F to 122
o
F).
Function 6
Max Supply Temp
Description: Allows the user to set the maximum design supply temperature based on the minimum
outdoor design temperature. Factory default 140
o
F (Range 77
o
F to 170
o
F).
Function 7
Max Outdoor Temp
Description: Allows the user to set the maximum outdoor design temperature for the system. Factory
default 68
o
F (Range 32
o
F to 95
o
F).
Function 8
Min Supply Temp
Description: Allows the user to set the design supply water temperature based on the maximum outdoor
design temperature. Factory default 120
o
F (Range 32
o
F to 200
o
F).
Function 9
Min Tank Temp
Description: Allows the user to set the minimum tank temperature. Factory default 68
o
F (Range 32
o
F to
200
o
F).
Function 10
CH Post Pump Time
Description: Allows the user to set the central heating pump post purge time once the thermostat is
satisfied. Factory default 0
minutes (Range 0 to 10
minutes).
Summary of Contents for Versa Hydro PHE130-119
Page 23: ...23 Figure 5 Figure 6 ...
Page 24: ...24 Figure 7 ...
Page 25: ...25 F HYDRONIC PIPING Figure 8 ...
Page 26: ...26 Figure 9 ...
Page 27: ...27 Figure 10 ...
Page 28: ...28 Figure 11 ...
Page 29: ...29 Figure 12 ...
Page 32: ...32 F INTERNAL WIRING Figure 14 Internal connection diagram ...
Page 38: ...38 Figure 17 ...
Page 48: ...48 Figure 25 ...
Page 76: ...76 Figure 29 ...
Page 77: ...77 Figure 30 ...
Page 78: ...78 Figure 31 LP 314 G ...
Page 79: ...79 Figure 32 ...
Page 81: ...81 ...
Page 82: ...82 ...
Page 83: ...83 MAINTENANCE NOTES ...