background image

 

 
 

 
 
 
 
 
 
 
 

 

 
 
 

Summary of Contents for P10A

Page 1: ......

Page 2: ...Installation and Instruction Manual Inverter Air Source Heat Pump ...

Page 3: ......

Page 4: ...e heat pump 2 The data of unit 5 6 9 10 10 11 11 12 12 13 27 31 31 11 1 Application of heat pump 2 Choose a right heat pump unit 3 Installation place 4 Installation method 5 Water loop connection 6 Power supply connection 7 Location of the unit 8 Transit 9 Trial Running 1 Main interface display and function 3 Interface diagram 1 Appendix 1 2 Appendix 2 4 Attention 4 25 2 Parameter list and breakdo...

Page 5: ...luded which is very easy for installation 3 Flexible installation The unit has smart structure with compact body just simple outdoor installation is needed This series of heat pump unit owns following features 1 Advanced controlling The PC microcomputer based controller is available for the users to review or set the running parameters of the heat pump Centralized controlling system can control se...

Page 6: ...on Compulsory implement The listed action need to be taken ATTENTION include WARNING Please pay attention to what is indicated Mark Notes Icon notes WARNING ATTENTION To prevent the users and others from the harm of this unit and avoid damage on the unit or other property and use the heat pump properly please read this manual carefully and understand the following information correctly Safety Prec...

Page 7: ...ff to stop the unit Continue to run may cause electrical short or fire Move and repair Entrust Prohibit Entrust When the heat pump need to be moved or installed again please entrust dealer or qualified person to carry it out Improper installation will lead to water leakage electrical shock injury or fire It is prohibited to repair the unit by the user himself otherwise electrical shock or fire may...

Page 8: ...e check the installation basement in a period one month to avoid any decline or damage on the basement which may hurt people or damage the unit Safety Precaution Meaning Fix the unit Installation Place Need circuit breaker The unit CANNOTbe installed near the flammable gas Once there is any leakage of the gas fire can be occur Make sure that the basement of the heat pump is strong enough to avoid ...

Page 9: ...ntlet tube Remote Controller Manually Water outlet tube The longest distance of installing the remote controller is 200 meters Water intlet tube Remote Controller Manually Water outlet tube P10A P10T P17A P17T The longest distance of installing the remote controller is 200 meters Water intlet tube Remote Controller Manually Water outlet tube ...

Page 10: ...415V 3N 50Hz 1 Rotary 1 75 850 0 05 52 42 55 1 1 7 5 5 P10A 3 220 11 300 1 270 4 640 4 700 12 50 1 080 3 440 5 760 16 20 1 160 4 200 4 640 21 5 220 240V 50Hz 1 Rotary 1 93 1050 0 05 52 42 55 1 1 7 5 5 P17A 5 500 15 50 1 500 6 000 7 000 20 50 1 500 6 000 9 350 24 30 2 060 6 400 7 200 33 2 220 240V 50Hz 1 Rotary 2 110 850 0 18 55 44 58 1 1 4 2 9 12 5 P17T 5 500 15 50 1 500 6 000 7 000 20 50 1 500 6 ...

Page 11: ...7 3 Unit dimension Specification Models P6 442 490 in 805 750 1002 392 332 155 65 915 423 460 700 953 in 357 85 706 128 Models P10A P10T ...

Page 12: ...8 3 Unit dimension Specification Models P17A P17T 997 650 395 437 1315 in 125 55 1030 Models P24T in 584 680 288 75 1605 397 450 1172 725 ...

Page 13: ...5 5 Remark Item 17 18 20 21 can be connected with heat pump Remark Item 17 18 20 21 can be connected with heat pump Relief valve Air vent valve Water pump for floor heating Check valve Floor heating valve Hot water tank Floor heating pipe fan coil unit Hot water valve Hot water pump Relief valve Air vent valve Water pump for floor heating Check valve Floor heating valve Hot water tank Floor heatin...

Page 14: ...ng chilled water outlet temp at 5 15 maximum ambient temp at 43 For heating warm water inlet temp at 40 50 minimum ambient temp at 25 Unit application a s w h p is used for house office hotel and so forth which need heating or cooling separately with each area need to be controlled Inverter ir ource ater eat ump There must be enough space around the unit for maintenance The place is free from heat...

Page 15: ...e thermometer and pressure meter at the water inlet and outlet for easy inspection during running There must be expansion tank on the top point of the water loop and the water level in the tank must be at least 0 5 meter higher than the top point of the water loop 6 Power supply connection Open the front panel and open the power supply access If the outside water pump is needed please insert the p...

Page 16: ...oller Check whether the water pump is running if it runs normally there will be 0 2 MPa on the water pressure meter When the water pump runs for 1 minutes the compressor will start Hear whether there is strange sound from the compressor If abnormal sound occurs please stop the unit and check the compressor If the compressor runs well please look for the pressure meter of the refrigerant 9 Trial Ru...

Page 17: ...Operation and Use 13 1 Main interface display and function 1 Power on interface 2 Starting up interface 13 13 11 11 12 12 14 14 1 0 1 0 11 12 13 14 ...

Page 18: ... there is an error shown up then the display will enter Failure record interface after tapping this icon is defrosting icon the machine is in defrosting mode when this icon is shown is electric heater icon the machine is in electric heater mode when this icon is shown is ambient temperature icon show the current ambient temperature is heating mode icon the machine is in cooling mode when this icon...

Page 19: ...On and off 1 In shutting down interface on off key is in gray status press on off key can start up the machine 2 Note In starting up interface on off key is in red status press on off key can shut down the machine As the main interface shows ...

Page 20: ...wn on the interface 4 tapping hot water heating mode icon then the display will go into hot water heating mode interface 5 tapping hot water cooling mode icon then the display will come to hot water cooling mode interface In the main interface there are five modes can be selected after tapping the mode key Take hot water cooling mode for example Tapping the wire controller back to main interface T...

Page 21: ...pping this key to undo the last action Note means the new target temp under current setting Tapping this key can save you action and back to the main interface 1 4 When the target temp is being set pop up keyboard is shown as following 1 5 Unlock screen Click the lock screen key again while the screen has been locked pop up keyboard is shown as following ...

Page 22: ...cked 1 6 Timer setting Click the timer setting key to enter the timer setting and the interface display is as follows Note Click to set the day of the week click to active the Timing switch function then click to select the morning or afternoon mode and finally click to select the time period to turn on the Timing switch ...

Page 23: ...ew the current operating parameters of the unit Click this key to turn on the unit Electric heating Operating mode Click the key and enter the password to enter the factory parameter settings and status parameters interface Click this key to set the system time Mute setting Curve key Click this key to set the unit mute function mode Click this key to view the temperature curve Note If the unit has...

Page 24: ...Operation and Use 20 In the setup interface 1 Tapping operating mode button then the interface display is shown as follows ...

Page 25: ...key to cancel the current settings and return to the settings page Click this key to save the current settings Enter key Up key Down key Click the up and dowm key to set the month Click the up and dowm key to set the day Click the up and dowm key to set the year Click the up and dowm key to set the hour Click the up and dowm key to set the minute Click the key to cancel the setting Click the key t...

Page 26: ...g the icon is displayed as While the unit is in cooling mode clicking the icon the electric heating will not be turned on While the unit is in hot water cooling mode if the hot water side is running the electric heating will be operated and shown if the cooling side is running clicking the icon the electric heating will not be turned on 4 Tapping Mute setting button then the interface display is s...

Page 27: ...played as 4 1 Tapping Mute Timer button then the interface display is shown as follows Note Click to set the day of the week click to active the mute mode then click to select the morning or afternoon mode and finally click to select the time period to turn on the silent mode 5 Tapping Curve button then the interface display is shown as follows 0h 0h 6h 6h 12h 12h 18h 18h 24h 24h ...

Page 28: ...urve to the current time point The leftmost point on the first page 0 on the abscissa is the latest temperature record 5 Temperature curve record is provided with power down memory function 1 7 Fault interface Click the fault icon on the main interface and the interface display is as follows Note Fault code Fault name Occurrence time of the fault Day and month hour minute second Click this key to ...

Page 29: ...he wire connection between DC fan motor module and fan motor is in badcontact 1 Change a new fan motor 2 Check the wire connection and make sure they are in good contact 1 Change a new fan motor 2 Check the wire connection and make sure they are in good contact Use side water system temp is low 1 Check the water temp or change the temp Sensor 2 Checkthe pipewater flowand whether watersystem is jam...

Page 30: ...itch is broken Check the pressure switch and cold circuit Check the pressure switch and cold circuit No water little water in water system Check the pipe waterflow and water pump The Fan Motor Fault Check the fan anddrive board The wire controller software is not match the mainboard software Check the wire control software number and the mainboard software number Speed control module and main boar...

Page 31: ...ower Device Overheat Fault F24 F26 Elimination methods Check and adjust the current measurement Check the measuring voltage check requency conversion board hardware Check the PFC switch tube short circuit or not Check the input voltage measurement Check the input voltage measurement Check the input voltage measurement Check the input voltage measurement Check and adjust the current measurement Che...

Page 32: ... 28 3 Interface diagram V R T A B G Sign Meaning V R T A B G 3 1 Wire control interface diagram and definition 12V power No use No use 485A 485B GND power 3 2 Controller interface diagram and definition PC4003 ZERO JP9 ...

Page 33: ...r flow detection No use Remote Heat Cool Heat Cool On Off No use No use No use No use System Exhaust temperature 1 DHW On Off Remote On Off Electric heating overload input Water flow switchprotection The low preesure switch 1 The high preesure switch 1 Temperature of the EVI outlet of system 1 Temperature of the EVI inlet of system 1 Room Temperature Water tank T emperature No use System1 Antifree...

Page 34: ...O08 RO07 RO06 RO05 RO04 RO03 RO02 RO01 No use No use No use Alarm output Chassis heating tape Crankshaft heating tape Hot water three way valve Electrical heating level 2 Electrical heating level 1 4 way valve Domestic hot water pump Main circulating water pump Fan low speed Fan high speed Compressor 1 ...

Page 35: ... life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This product is compliant with directive 2002 95 EC RoHs concerning restrictions for the use of harmful substances in electric and electronic devices 7 The unit CANNOT be install...

Page 36: ...hase line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm 2 mm 25 2 mm 25 2 35mm 2 50mm 2 70mm 2 95mm 2 Three phase unit 2 3 1 5mm 2 3 2 5mm 2 3 4mm 2 3 6mm 2 3 10mm 2 16mm 3 2 25mm 3 2 3 25mm 2 3 35mm 2 3 50mm 2 3 70mm 2 3 95mm 30mA less than 0 1 sec 3...

Page 37: ...Code 20200925 0001 ...

Reviews: