FULLTEST
3
EN - 86
TRMS Residual voltage (U
RES
)
Display range
Resolution
(V)
Accuracy
(general)
Overvoltage protection
10
460 V
1
± (3% rdg. + 3 V)
CAT III 300 V
10
650 V
Input voltage (U
TRIG
): 0
460 V AC
Nominal mains voltage :
230 or 240 V
Measurement method:
4-wire connection (INTERNAL measurement, 1 s or 5 s)
2-wire connection (PLUG measurement, 1 s)
Residual voltage limit value:
60 V RMS
Input voltage U
RES
:
Display range
(V)
Resolution
(V)
Accuracy
10
460 V AC
1
± (2% rdg. + 2 V)
10
650 V DC
Input resistance (U
RES
): 100
M
Input voltage U
TRIG
:
Display range
(V)
Resolution
(V)
Accuracy
10
265 V AC
1
± (2% rdg. + 2 V)
Input resistance (U
TRIG
): 450
k
TRMS Load Current (POWER)
Display range
A
Resolution
A
Accuracy
Overvoltage protection
0.00
0.99
0.01
± (3% rdg. + 3 dgt)
CAT II 300 V
1.0
20.0
0.1
Frequency range
15
723 Hz
Over-range limit
Yes, the measurement will be automatically interrupted 10 s
after exceeding 16 A
Pre-Test
Grounding of PE terminal on wall schuko socket
TRMS Mains Voltage (POWER)
Display range
V
Resolution
V
Accuracy
Overvoltage protection
195
253
1
± (2% rdg. + 2 dgt)
CAT II 300 V
Frequency range
15
723 Hz
Apparent Power / Active Power (POWER)
Display range
VA/W
Resolution
VA/W
Accuracy
Overvoltage protection
0.0
99.9
0.1
± (5% rdg. + 10 dgt)
CAT II 300 V
100
999
1
± (5% rdg. + 3 dgt)
1.00
5.06 k
10
Limit value P
APP
Adjustable
6
999 VA, 1.00 kVA
5.06 kVA