FULLTEST
3
EN - 34
8 .....
PROT.
(protection) touch-screen key to select the type of protection (MCB B, MCB C, MCB D,
MCB K, FUSE gG or FUSE aM) and nominal current of selected protection. Currently selected type
is displayed on the bottom of the key.
9 .....
WIRE
touch-screen key to select the material of measured wire (Cu or Al), coating (PVC, BUTYL
RUBBER or EPR/XLPE), section (1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50,
70, 95, 120, 150, 185, 240,
300, 400, 500 or 630
mm
2
) and number of conductors (1
99). Currently selected material is
displayed on the bottom of the key.
10 ... Measurement result (in green colour - result OK, in red colour - result not OK).
11 ... Real time clock (hh.mm.ss).
12 ... Unit of the test result (
).
13 ... Measurement result status (symbol
in green colour - result OK, symbol
in red colour - result
not OK).
5.6.2. LIMIT VALUE EXPLANATION
There are five possibilities to select the limit prospective short-circuit current I
SC LIM
, which is the bases
for final evaluation.
STD
- no verification.
No limit is used in this case meaning test result is not evaluated and is therefore always considered as
neutral (displayed in white colour).
kA
- verification if short-circuit current is lover than breaking capacity of involved over-current protection
device.
Measured I
SC MAX
must be lower or equal than entered breaking capacity Ib of involved over-current
protection device, where breaking capacity Ib can be selected among the following values:
-
Ib (breaking capacity)
1, 1.5, 3, 4.5, 6, 10, 15, 16, 20 or 25 kA
I
2
t
- verification if over-current protection device reacts before wires are overheated and thus damaged.
On bases of measured I
SC MAX
and entered over-current protection device (PROTECTION) and
nominal current of the over-current protection device (In) trip out time of the over-current protection
device (t) is calculated. See the evaluation equation in the table “PROSPECTIVE SHORT-CIRCUIT
CURRENT CALCULATION” below. Entered parameters can be selected among the following values:
-
PROT (type of protection)
MCB B, MCB C, MCB D, MCB K, FUSE gG or FUSE aM
-
In (nominal current)
- 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB B)
- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB C)
- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25 or 32 A (MCB D, MCB K)
- 2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,
200, 250, 315, 400, 500, 630, 800, 1000 or 1250 A (FUSE gG)
- 2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,
200, 250, 315, 400, 500 or 630 A (FUSE aM)
-
MATERIAL (wire material)
Cu (Cupper) or Al (Aluminium)
-
COATING (wire coating)
PVC, BUTYL RUBBER or EPR/XLPE
-
SECTION (wire section)
1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50,
70, 95, 120, 150, 185, 240,
300, 400, 500 o 630
mm
2
-
N (number of conductors)
1
99
TRIP CURRENT
- verification if over-current protection device reacts within set time at measured short-
circuit current.
On bases of measured I
SC MIN
and entered over-current protection device (PROTECTION) and nominal
current of the over-current protection device (In) trip out time is calculated which must be lower than or
equal to entered Tset. Entered parameters can be selected among the following values: