5.5.3. RCD MEASUREMENT
Measured quantities and display ranges:
Trip out time at I
N
/2
0
1000 ms (AC, A, B, general, selective, delayed)
Trip out time at I
N
0
1000 ms (AC, A, B, general, selective, delayed)
Trip out time at 2I
N
0
200 ms (AC, A, general), 0
250 ms (AC, A, selective)
Trip out time at 4I
N
0
200 ms (B, general), 0
250 ms (B, selective)
Trip out time at 5I
N
0
50 ms (AC, A, general), 0
150 ms (AC, A, selective)
AUTO test
YES (general, selective)
Trip out current (Ramp test)
10
110% of I
N
in steps of 5% of I
N
(general)
Input requirements:
Mains voltage U
L/N
(READY condition)
100
265 V AC
Mains voltage U
L/PE
(READY condition)
100
265 V AC
1)
Select the RCD function by pressing the
FUNC
hard key first.
2)
Check selected RCD type (AC, A or B) and selected characteristic (GENERAL, SELECTIVE or
DELAYED) and modify it if needed by pressing the
TYPE
(5) touch-screen key first. If DELAYED
characteristic is selected, the screen will turn to delay time adjustment mode automatically.
3)
Select nominal differential current by pressing the
I
N
touch-screen key first.
4)
Select wished measurement by pressing the
MEAS
touch-screen key first (t
/1/2I
N
, t
/I
N
, t
/2I
N
,
t
/5I
N
, I
or AUTO).
5)
Check selected polarity and modify it if needed by pressing the
POL
(8) touch-screen key first.
6)
Select measurement screen by pressing the
(4) touch-screen key and check all settings again.
7)
Connect the test leads according to one of the figures below.
Figure 21: Connection of schuko test cable
Figure 22: Connection of test leads