3. Place the end of the 15.24-cm (6-inch) grounding strap over the grounding lug on the top side panel.
4. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the top side panel, and then
tighten the washer.
5. Repeat steps 1 through 4 for the other top side panel.
Installing the ground bonding kit on fan kits
Procedure
1. Place one end of a 15.24-cm (6-inch) grounding strap over the grounding lug on the rack top.
2. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the rack top. Then, tighten the
washer.
3. Place the other end of the same grounding strap over the grounding lug on the perforated panel.
4. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the perforated panel. Then,
tighten the washer.
Ground Bonding kit