NOTE: The screw holes for the cross-over bracket are located on the side of the rear rack screw column, towards the inside
of the rack.
2. Using a T-25 Torx driver, insert two M5.5 x 10-mm Torx screws on each side of the cross-over bracket and secure to the
rack frame (2).
Installing the hook-and-loop cabling straps
Attach the clip to the rack in any of the following positions, then route and secure your cables with the hook-and-loop cabling
straps.
Cable Management Combo kit
25
NOTE:
To avoid interference with the rear door lock, do not install in the following U range if the rear door will be closed.
Prohibited U heights
Rack
22U
07U~16U
36U
14U~23U
42U
16U~27U
48U
20U~29U
Summary of Contents for G2 Series
Page 16: ...Ballast kit 16 ...
Page 19: ...5 Re attach the front and rear doors Baying kits 19 ...
Page 26: ...Cable Management Combo kit 26 ...
Page 29: ...Rack Roof Mount Fan kit 29 ...
Page 42: ...Hook and Loop Cabling Strap Clip kit 42 ...
Page 43: ...Hook and Loop Cabling Strap Clip kit 43 ...
Page 45: ...4 Bundle rack cables as required 1 4 Turn Hook and Loop Cabling Strap kit 45 ...
Page 57: ...Server Utility Shelf kit 57 ...
Page 65: ...Side Panel kit 65 ...
Page 68: ...5 Tighten the bolts from steps 2 and 4 Stabilizer kit 68 ...