Parameter 62 (2GG) – DHW charging (switch / pump) –
This parameter defines whether a pump is present for
DHW charging or whether only a switch is in use in addi-
tion to the main pump.
The setting "0" means a KKP (pump output) and additio-
nally a switch (switch output) is used. The setting "1"
means, that the pump at the pump output (X8-5/6) is only
work ing in heating mode and the DHW pump at the out-
put X8-7/8 is getting active in the DHW mode.
Parameter 63 (2GH) – pump – minimum PWM value –
This parameter specifies the minimum permissible out
-
put of the PWM pump in %. The minimum PWM value is
applied in the case of minimum boiler output. The pump
speed increases in linear manner between minimum and
maximum boiler output.
Parameter 64 (2GI) – pump - maximum PWM value –
This parameter specifies the maximum permissible out
-
put of the PWM pump in %. The maximum PWM value is
ap plied in the case of maximum boiler output. The pump
speed increases in linear manner between minimum and
maximum boiler output.
Parameter 65 (2GJ) – three-way valve inverted –
The output for controlling the three-way valve can be in-
ver ted via this parameter.
Parameter 66 (2EO) – Air pressure switch fitted –
Setting this parameter specifies whether air pressure
switches are installed for monitoring the air channels in
the boiler or not.
0
no air pressure switches are installed
1
air pressure switches are installed