11
4 219 316 / 00
TECHnICaL InFORMaTIOn
Type
(80)
(100)
(120)
• Nominal heat output at 80/60 °C, natural gas
kW
13.4-71.8
18.6-91.2
20.7-109.7
• Nominal heat output at 50/30 °C, natural gas
kW
14.8-79.1
20.7-100.0
22.9-120.5
• Nominal heat output at 80/60 °C, propane
2)
kW
18.4-73.7
22.9-90.4
23.7-107.6
• Nominal heat output at 50/30 °C, propane
2)
kW
20.3-79.9
25.3-100.0
26.1-120.0
• Nominal heat input with natural gas
1)
kW
13.8-75.8
19.2-93.7
21.1-114.0
• Nominal heat input with propane
2)
kW
19.0-74.4
23.7-93.0
24.6-111.5
•
Heating operating pressure min./max. (PMS)
bar
1/4
1/4
1/4
• Test pressure (PT)
bar
6
6
6
• Operating temperature max. (T
max
)
°C
85
85
85
• Boiler water content (V
(H20)
)
l
5.4
7.0
7.0
• Flow resistance boiler
z-value
see diagram
•
Minimum circulation water quantity
l/h
550
800
800
• Boiler weight (without water capacity, incl. casing)
kg
116
130
130
•
Boiler efficiency at 80/60 °C in full-load operation (NCV/GCV)
%
96.3/86.8
97.8/88.2
98.6/88.9
•
Boiler efficiency at 30 % partial load (EN 15502) (NCV/GCV)
%
107.8/97.3
107.6/97.0
106.1/95.8
•
Room heating energy efficiency
- without control
ηs
%
92
92
91
- with control
ηs
%
94
94
93
- with control and room sensor
ηs
%
96
96
95
• NOx class (EN 15502)
6
6
6
• Nitrogen oxide emissions (EN 15502) (GCV)
NOx
mg/kWh
29.0
27.8
31.1
• Content of CO
2
in the flue gas minimum/maximum output
%
8.8/8.8
8.8/8.8
9.2/8.8
• Heat loss in standby mode
Watt
105
115
115
• Dimensions
see table of dimensions
•
Gas flow pressure minimum/maximum
- Natural gas E/LL
mbar
17.4-50
17.4-50
17.4-50
- Propane
mbar
37-50
37-50
37-50
• Gas connection value at 15 °C/1013 mbar:
- Natural gas E (Wo = 15.0 kWh/m
3
) NCV = 9.97 kWh/m
3
m
3
/h
1.4-7.6
1.9-9.4
2.1-11.4
- Natural gas LL (Wo = 12.4 kWh/m
3
) NCV = 8.57 kWh/m
3
m
3
/h
1.6-8.8
2.2-10.9
2.5-13.3
- Propane
2)
(NCV
= 25.9 kWh/m
3
)
m
3
/h
0.7-2.9
0.9-3.6
0.9-4.3
• Operation voltage
V/Hz
230/50
230/50
230/50
• Electrical power consumption min./max.
Watt
23/116
22/150
22/214
• Stand-by
Watt
6
6
6
• Type of protection
IP
40D
40D
40D
• Permitted ambient temperature during operation
°C
5-40
5-40
5-40
• Sound power level
- Heating noise (EN 15036 Part 1) (room air dependent)
dB(A)
63
63
63
• Condensate quantity (natural gas) at 50/30 °C
l/h
7.1
8.9
10.3
• pH value of the condensate
4-6
4-6
4-6
• Construction type
B23, C13(x), C33(x), C53(x), C63(x), C93(x)
• Flue gas system
- Temperature class
T120
T120
T120
-
Flue gas mass flow at nominal heat load (dry)
kg/h
124
152
187
-
Flue gas mass flow at lowest nominal heat load (dry)
kg/h
20.9
29.2
32
- Flue gas temperature at nominal output and operation 80/60 °C
°C
62.7
62.6
66.8
- Flue gas temperature at nominal output and operation 50/30 °C
°C
43.9
43.2
46
- Flue gas temperature at lowest nominal heat load and operation 50/30 °C °C
30
29.8
30.3
-
Maximum permitted temperature of the combustion air
°C
50
50
50
-
Volume flow rate combustion air
Nm
3
/h
102
125
153
-
Maximum supply pressure for supply air and flue gas line
Pa
140
140
140
-
Maximum draught/depression at flue gas outlet
Pa
-50
-50
-50
1)
Data related to NCV.
The boiler series is tested for EE/H-settings. With a factory setting of the Wobbe coefficient of 15.0 kWh/m
3
operation at a Wobbe coefficient of 12.0 up to 15.7 kWh/m
3
is possible without new settings.
2)
Data related to NCV. TopGas
®
classic can also be operated with propane.