16
4 219 316 / 00
TECHnICaL InFORMaTIOn
Entering the service code
To set the code, the "Mode" and "Step" keys must be
pres sed at the same time. The digit which flashes can
be chang ed using the "+" and "-" keys. The "Step" key
is us ed to switch between the digits. The complete code
is con fir med and saved with the "Store" key. The screen
automatically switches back to the display level after 20
minutes.
Function
Mode indication
Parameter indication
Value indication
Meaning, description
Information Mode
It is possible
to read current values
from here
Point is blinking
0
e.g. 45°
Current flow temperature
(heating water temperature)
1
e.g. 40°
Current return temperature
2
e.g. 60°
Current temperature in the calorifier
3
e.g. 3°
Current outside temperature
4
e.g. 55°
Current flue gas temperature
5
e.g. 50°
Flow temperature set value in heating operation
6
e.g. 70°
Flow temperature set value in domestic hot water
mode
7
e.g.23 RPM
Fan speed in hundred rpm
8
e.g. 4 µ A
Ionisation current
Parameter Mode
Settings can be changed
in this mode.
Point appears
P. 7
60
= Set value, DHW charging
if there is no TopTronic
®
attached
Procedure:
P. 18
80
= Maximum heating temperature (at minimum
outdoor temperature) during heating operation
1. Select parameter mode
(press mode key twice)
The parameter (P.7) and the
setting value are displayed
alternately.
Parameter 18
Flow temperature
Outside
temperature
Further parameters only with service code
2. Select the parameter
to be changed (step key)
3. Change setting using + - keys
4. Save
(press store key once)
Return to standby mode
automatically after 20 minutes
or by pressing mode key.
Parameter level (constant dot)
Parameter level is indicated by a constant dot after the
second character.
If neither the "+" or the "-" key is pressed, "P" + parameter
number and then the corresponding parameter value are
dis played alternately. The corresponding parameter value
can be changed by pressing the "+" or "-" key. Changes
ma de are saved by pressing "Store" and are confirmed
by the display flashing twice - (wait for this flashing signal
be fore pressing another key!). If the "Store" key is not
pres sed, the setting is not applied.