10
4 219 316 / 00
TECHnICaL InFORMaTIOn
2.3
Technical data for TopGas
®
classic (35-120)
Type
(35)
(45)
(50)
(60)
• Nominal heat output at 80/60 °C, natural gas
kW
6.9-31.7
8.3-39.8
14.6-48.3
11.9-54.1
• Nominal heat output at 50/30 °C, natural gas
kW
7.4-34.9
9.1-44.3
16.0-52.0
12.8-60.3
• Nominal heat output at 80/60 °C, propane
2)
kW
9.5-32.5
10.4-41.5
-
14.1-56.6
• Nominal heat output at 50/30 °C, propane
2)
kW
10.5-36.3
11.45-45.8
-
15.5-61.1
• Nominal heat input with natural gas
1)
kW
6.9-33.0
8.5-42.4
15.0-49.0
11.7-56.9
• Nominal heat input with propane
2)
kW
9.8-33.0
10.7-42.1
-
14.5-57.7
•
Heating operating pressure min./max. (PMS)
bar
1/4
1/4
1/4
1/4
• Test pressure (PT)
bar
6
6
6
6
• Operating temperature max. (T
max
)
°C
85
85
85
85
• Boiler water content (V
(H20)
)
l
4.0
4.0
5.4
5.4
• Flow resistance boiler
z-value
see diagram
•
Minimum circulation water quantity
l/h
300
350
390
470
• Boiler weight (without water capacity, incl. casing)
kg
96
96
116
116
•
Boiler efficiency at 80/60 °C in full-load operation (NCV/GCV)
%
97.6/88.1
95.7/86.3
97.2/87.7
97.0/87.5
•
Boiler efficiency at 30 % partial load (EN 15502) (NCV/GCV)
%
107.4/96.6
107.3/96.8
107/96.6
107.3/96.8
•
Room heating energy efficiency
- without control
ηs
%
92
92
92
92
- with control
ηs
%
94
94
94
94
- with control and room sensor
ηs
%
96
96
96
96
• NOx class (EN 15502)
6
6
6
6
• Nitrogen oxide emissions (EN 15502) (GCV)
NOx
mg/kWh
23.9
27.4
21.8
23.4
• Content of CO
2
in the flue gas minimum/maximum output
%
8.7/9.0
8.8/8.9
9/8.8
8.8/8.8
• Heat loss in standby mode
Watt
95
95
105
105
• Dimensions
see table of dimensions
•
Gas flow pressure minimum/maximum
- Natural gas E/LL
mbar
17.4-50
17.4-50
17.4-50
17.4-50
- Propane
mbar
37-50
37-50
37-50
37-50
• Gas connection value at 15 °C/1013 mbar:
- Natural gas E (Wo = 15.0 kWh/m
3
) NCV = 9.97 kWh/m
3
m
3
/h
0.7-3.3
0.9-4.3
1.5-4.9
1.2-5.7
- Natural gas LL (Wo = 12.4 kWh/m
3
) NCV = 8.57 kWh/m
3
m
3
/h
0.8-3.9
1.0-4.9
1.8-5.7
1.4-6.6
- Propane
2)
(NCV
= 25.9 kWh/m
3
)
m
3
/h
0.4-1.3
0.4-1.6
-
0.6-2.2
• Operation voltage
V/Hz
230/50
230/50
230/50
230/50
• Electrical power consumption min./max.
Watt
24/74
24/78
23/68
23/78
• Stand-by
Watt
6
6
6
6
• Type of protection
IP
40D
40D
40D
40D
• Permitted ambient temperature during operation
°C
5-40
5-40
5-40
5-40
• Sound power level
- Heating noise (EN 15036 Part 1) (room air dependent)
dB(A)
61
61
63
63
• Condensate quantity (natural gas) at 50/30 °C
l/h
3.7
4.3
4.5
5.4
• pH value of the condensate
4-6
4-6
4-6
4-6
• Construction type
B23, C13(x), C33(x), C53(x), C63(x), C93(x)
• Flue gas system
- Temperature class
T120
T120
T120
T120
-
Flue gas mass flow at nominal heat load (dry)
kg/h
52.5
66.4
76.1
88.4
-
Flue gas mass flow at lowest nominal heat load (dry)
kg/h
10.5
13
23.3
17.8
- Flue gas temperature at nominal output and operation 80/60 °C
°C
57.7
59.4
57.6
58.9
- Flue gas temperature at nominal output and operation 50/30 °C
°C
36.7
40.5
36.3
38.6
- Flue gas temperature at lowest nominal heat load and operation 50/30 °C °C
28.8
28.9
29.4
29.4
-
Maximum permitted temperature of the combustion air
°C
50
50
50
50
-
Volume flow rate combustion air
Nm
3
/h
42.9
54.2
62.4
72.4
-
Maximum supply pressure for supply air and flue gas line
Pa
120
120
140
140
-
Maximum draught/depression at flue gas outlet
Pa
-50
-50
-50
-50
1)
Data related to NCV.
The boiler series is tested for EE/H-settings. With a factory setting of the Wobbe coefficient of 15.0 kWh/m
3
operation at a
Wobbe coefficient of 12.0 up to 15.7 kWh/m
3
is possible without new settings.
2)
Data related to NCV. TopGas
®
classic can also be operated with propane.