3. Operation
3.1 Functional characteristics, functional parts and control elements
The BioLyt (10-26) pellet boiler and the TopTronic
®
T heating control system form a perfect unit. The BioLyt
(10-26) will start up automatically every time the control system requires the burner to operate. Once the pre-
purge (safety function) has been completed, the ignitor is switched on and the pellet metering screw starts
operating. The burner pot is filled with pellets automatically. Once a flame has been detected (combustion
chamber temperature sensor), the boiler goes into control mode (modulated control), where it automatically
maintains the predefined boiler setpoint temperature (60-75°C). The boiler goes into burnout mode if the
extracted heat falls below the minimal boiler output or when there is no heat requirement from the control
system. The fan continues to operate until the burner pot has cooled down.
3.1.1 BioLyt Standard
The storage container is loaded manually (or, upon request, fully automatically). The heating surfaces are
manually cleaned with the help of cleaning levers. Any cleaning residues from the heating surfaces as well
as the combustion residues from the burner pot fall into the ash pan.
BioLyt Standard without combustion chamber door and with open cladding door
InfoDisplay control unit
Front cladding cover
Rear cladding cover
Safety thermostat for
boiler temperature
Safety thermostat for
screw tube
Heating surface lever
Deflector plate
Collection channel
Burner pot
Ash pan
Fully automatic pellet
feed (option)
Top inspection cover
Bottom inspection cover
Pellet storage container
Cleaning brush
Spatula
Cone removal tool
Cladding door
Screw motor
Water tank level indicator
3. Operation
TopTronic
®
T heating
control system
Fig. 2
5
4 204 827 / 02