47

D. 

Defrost Termination: Defrost Completion

1a) 

Freezer (auxiliary code P-5 and earlier)–LEDs 4 (Comp) and 5 (ConFM) are 

on. LED 3 (EvapFM on) off:

 When CTh reads 15

°

F (8.3

°

C) above setpoint or less, 

cabinet temperature is displayed on DB. Defrost is complete.

1b) 

RFH1-SSB(-HS)(-HSE) Freezer–LEDs 4 (Comp and ConFM) and 5 (DrH, PH, 

and MH) are on. LED 3 (EvapFM on) off: 

When CTh reads 15

°

F (8.3

°

C) above 

setpoint or less, cabinet temperature is displayed on DB. Defrost is complete.

 

Legend: 

CB

–control board; 

ConFM

–condenser fan motor; 

Comp

–compressor;             

CTh

–cabinet thermistor; 

DB

–display board;  

DH

–defrost heater; 

DrH

–drain heater; 

DT

–defrost thermostat; 

DTh

–defrost thermistor; 

EvapFM

–evaporator fan motor; 

MH

–mullion heater; 

PH

–perimeter heater; 

TXV

–thermostatic expansion valve

2b. Freezer (auxiliary code P-6 and later) and RFH1-SSB-HD Freezer

7) 

Startup–No component LEDs are on. LED 3 (EvapFM on) is off: 

EvapFM energizes. 

2.5 min. Comp delay timer starts. Cabinet temperature appears on DB.

a) 

EvapFM Diagnosis: 

If EvapFM does not energize, make sure "door" is not 

displayed on DB. If so, check that CB dip switch #3 is in the factory default position. 

See, "II.E.4.c) Door Switch Type (S3 dip switch 3)." Check door switch continuity. 

Next, check for 115VAC at CB K1 connector pin #3 (DBU wire) to a neutral (W wire). 
If 115VAC is not present, replace CB. If 115VAC is present, check EvapFM blade for 
binding and EvapFM continuity.

8a) 

Cool Down–Freezer: LEDs 4 (Comp) and 5 (ConFM) are on (except RFH1-SSB-HD). 

LED 3 (EvapFM on) is off: 

2.5 min. Comp delay timer terminates. EvapFM continues. 

Comp and ConFM, energize. 2.5 min. Comp minimum run timer starts.

8b) 

Cool Down–RFH1-SSB-HD Freezer:LED 4 (Comp and ConFM) is on. LED 3 

(EvapFM on) is off. LED 5 (CPH and DrH) is on after first cool down cycle: 

2.5 min. 

Comp delay timer terminates. EvapFM continues. CPH and DrH continue (after first cool 
down cycle). Comp and ConFM, energize. 2.5 min. Comp minimum run timer starts. 

a)

 Comp Diagnosis:

 Check that Comp energizes. If Comp does not energize, check 

for 115VAC at CB K1 connector pin #10 (GY wire) to a neutral (W wire). If 115VAC is 
not present, replace CB. If 115VAC is present, check for 115VAC at Comp relay black 
(BK  wire) and red (R wire) to a neutral (W wire). If 115VAC is not present on the 
black (BK wire), check wiring connections. If 115VAC is present on black (BK wire) 
but not on the red (R wire), Comp relay contacts are open. Confirm 115VAC on Comp 
relay coil gray (GY wire) to a neutral (W wire). If 115VAC is present, and contacts 
are open, replace Comp relay. Next, if 115VAC is present on the red (R wire), check 
continuity of Comp overload. If overload is closed, check start capacitor, start relay, 
and Comp motor winding. If overload is open, let overload cool and reset. Replace 
overload if it does not reset. When overload closes, if Comp still does not start, check 
start capacitor, start relay, and Comp motor winding.

Summary of Contents for FH1-SSB(-HD)

Page 1: ... A Superior Degree of Reliability www hoshizaki com Models SSB Professional and TempGuard Series Refrigerated Kitchen Equipment Hoshizaki America Inc Number 73077 Issued 3 8 1999 Revised 5 22 2012 SERVICE MANUAL ...

Page 2: ...arranty Hoshizaki provides this manual primarily to assist qualified service technicians in the service and maintenance of the appliance Should the reader have any questions or concerns which have not been satisfactorily addressed please call send an e mail message or write to the Hoshizaki Technical Support Department for assistance Phone 1 800 233 1940 770 487 2331 Fax 1 800 843 1056 770 487 336...

Page 3: ...c Temperature Display Scale F or C 29 2 Service Menu 30 3 LED Lights and Alarm Safeties Chart 31 4 Default Dip Switch Settings 33 a Appliance Operation Freezer Refrigerator S3 dip switch 1 34 b Cabinet Light Heated Glass Door S3 dip switch 2 34 c Door Switch Type S3 dip switch 3 34 d Refrigerator Defrost Initiation Temperature S3 dip switch 4 34 e Display Board Operation S3 dip switch 5 35 f Dual ...

Page 4: ...itch 54 E Diagnostic Chart 55 IV Replacement of Components 57 A Service for Refrigerant Lines 57 1 Refrigerant Recovery 57 2 Brazing 58 3 Evacuation and Recharge R 404A 58 B Important Notes for Component Replacement 59 C Removal and Replacement of Evaporator Fan Shroud Assembly 60 D Removal and Replacement of Heat Shield on FH2 SSB HD 61 E Removal and Replacement of Door Closure Spring 62 F Door R...

Page 5: ...ode T 5 to V 5 78 F3 RH3 SSB FG HG auxiliary code A 5 and later 79 G1 FH1 SSB HD auxiliary code P 5 and earlier 80 G2 FH1 SSB HD auxiliary code P 6 to S 5 81 G3 FH1 SSB HD auxiliary code S 6 and later 82 H1 FH2 SSB HD auxiliary code P 5 and earlier 83 H2 FH2 SSB HD HDCU auxiliary code P 6 and later 84 I RFH1 SSB HD 85 1 Refrigerator 85 2a Freezer auxiliary code P 5 and earlier 86 2b Freezer auxili...

Page 6: ...c precautions including the following Only qualified service technicians should install and service this appliance This appliance must be installed in accordance with applicable national state and local codes and regulations For Power Cord Models This appliance requires an independent power supply of proper capacity See the nameplate for electrical specifications Failure to use an independent powe...

Page 7: ...se or damage to existing wiring This could lead to heat generation or fire To reduce the risk of electric shock do not touch the power switch with damp hands Before servicing move the power switch to the OFF position and turn off the power supply Lockout Tagout to prevent the power supply from being turned back on inadvertently THIS APPLIANCE MUST BE GROUNDED Failure to properly ground this applia...

Page 8: ...ot put warm or hot foods in the cabinet Let them cool first or they will raise the cabinet temperature and could deteriorate other foods in the cabinet or overload the appliance All foods should be wrapped in plastic film or stored in sealed containers Otherwise foods may dry up pass their smells onto other foods cause frost to develop result in poor appliance performance or increase the likelihoo...

Page 9: ...0 21 5 oz PTR2SSB FGFG HGHG 115 60 1 12 8 450 250 17 3 oz RIR1 SSB 115 60 1 7 0 450 200 12 2 oz RIR2 SSB 115 60 1 11 0 450 200 18 2 oz RIR2 SSB51 02 115 60 1 11 0 450 200 18 2 oz RTR1 SSB 115 60 1 7 0 450 200 12 2 oz Design Pressure PSIG Refrigerant Model AC Supply Voltage Amperes Refrigerator Freezer R 404A R 134a HI LO HI LO Ref Freezer Ref RFH1 SSB HD 115 60 1 16 0 450 250 450 250 9 5 oz 12 0 o...

Page 10: ...er Condenser Air Filter Display Board Top Cover Front Panel Door Door Lock Door Gasket Control Box Power Switch Perimeter Heater Switch Door Latch Cabinet Thermistor Defrost Thermistor Evaporator Case Cover Control Box Cover Model Shown RH1 SSB FG Light Switch glass door model Door Switch Compressor Thermostatic Expansion Valve ...

Page 11: ...enser Condenser Air Filter Display Board Top Cover Front Panel Door Door Lock Door Gasket Control Box Power Switch Thermostatic Expansion Valve Cabinet Thermistor Defrost Thermistor Evaporator Case Cover Control Box Cover Door Switch Compressor Model Shown RH2 SSB Perimeter Heater Switch ...

Page 12: ...ilter Display Board Top Cover Front Panel Door Door Lock Door Gasket Control Box Power Switch Thermostatic Expansion Valve Cabinet Thermistor Defrost Thermistor Evaporator Case Cover Control Box Cover Door Switch Compressor Model Shown RH3 SSB FG Door Handle Perimeter Heater Switch Light Switch glass door model ...

Page 13: ...r Filter Display Board Top Cover Front Panel Door Door Lock Door Gasket Control Box Power Switch Thermostatic Expansion Valve Cabinet Thermistor Defrost Thermistor Evaporator Case Cover Control Box Cover Door Switch Compressor Model Shown PTR2SSB FGFG Perimeter Heater Switch Light Switch glass door model ...

Page 14: ...nser Air Filter Display Board Top Cover Front Panel Door Door Lock 3 Sided Door Gasket Control Box Power Switch Thermostatic Expansion Valve Cabinet Thermistor Evaporator Case Cover Control Box Cover Door Switch Compressor Model Shown RIR1 SSB Rack Guide Ramp Perimeter Heater Switch Sweep Gasket ...

Page 15: ... Condenser Air Filter Display Board Top Cover Rear Panel Door Door Lock Door Gasket Control Box Power Switch Thermostatic Expansion Valve Cabinet Thermistor Evaporator Case Cover Control Box Cover Door Switch Compressor Model Shown RTR1 SSB Front Panel Rack Guide Ramp Perimeter Heater Switch ...

Page 16: ...5 ConFM are on EvapFM continues 2 5 minute Comp delay timer terminates Comp and ConFM energize 2 5 min Comp minimum run timer starts 2b Cool Down RFH1 SSB HD HS HSE Refrigerator LEDs 4 Comp and ConFM and 5 unused are on EvapFM continues 2 5 minute Comp delay timer terminates Comp and ConFM energize 2 5 min Comp minimum run timer starts 3 Cool Down Achieved No Component LEDs are on LED 3 EvapFM on ...

Page 17: ...A1 Temperature Initiation above B Defrost Termination 1 Refrigerator LEDs 4 Comp and 5 ConFM are on LED 3 EvapFM on is off DTh warms to 40 F 4 C EvapFM and ConFM continue 2 5 minute Comp delay timer terminates Comp energizes 2 RFH1 SSB HD HS HSE Refrigerator LEDs 4 Comp and ConFM and 5 unused are on LED 3 EvapFM on is off DTh warms to 40 F 4 C EvapFM continues 2 5 minute Comp delay timer terminate...

Page 18: ...Dip switch 8 is only used on RFH1 SSB HD model 2a Cool Down Freezer auxiliary code P 5 and earlier LEDs 4 Comp and 5 ConFM are on LED 3 EvapFM on is off 2 5 minute Comp delay timer terminates Comp ConFM and EvapFM energize 2b Cool Down Freezer auxiliary code P 6 and later LEDs 4 Comp and 5 ConFM are on LED 3 EvapFM on is off 2 5 minute Comp delay timer terminates EvapFM continues Comp and ConFM en...

Page 19: ...y code Q 5 and later continue Comp and ConFM energize 4d Cool Down Restart RFH1 SSB HS HSE Freezer LEDs 4 Comp and ConFM and 5 DrH PH and MH are on LED 3 EvapFM on is off CTh warms to 3 F 1 7 C above setpoint 2 5 minute Comp delay timer terminates Comp ConFM EvapFM DrH PH and MH energize 5a Defrost Freezer auxiliary code P 5 and earlier and RFH1 SSB HS HSE Freezer 1 Time Initiated Defrost or Manua...

Page 20: ...reezer auxiliary code P 5 and earlier LEDs 4 Comp and 5 ConFM are on LED 3 EvapFM on is off DTh cools to 70 F 21 C or lower EvapFM energizes a2 RFH1 SSB HS HSE Freezer LEDs 4 Comp and ConFM and 5 DrH PH and MH are on LED 3 EvapFM is off DTh cools to 70 F 21 C or lower EvapFM energizes 4 Defrost Completiton a1 Freezer auxiliary code P 5 and earlier LEDs 4 Comp and 5 ConFM are on LED 3 EvapFM on off...

Page 21: ...ing contact Hoshizaki Technical Support at 1 800 233 1940 for recommendations Note Some models may utilize any combination of the following heaters during defrost Duct Heater Cord Heater or Drain Heater See VII Wiring Diagrams for specific model details 2 Defrost Termination Defrost Recovery Step 1 a1 Freezer auxiliary code P 6 and later LEDs 3 EvapFM off 4 Comp and 5 ConFM are on DTh warms to 100...

Page 22: ...and DrH auxiliary code Q 5 and later are on LED 3 EvapFM on is off When CTh reads 15 F 8 3 C above setpoint or less cabinet temperature is displayed on DB Defrost is complete Legend CB control board Comp compressor ConFM condenser fan motor CordH cord heater CPH condensate pan heater CTh cabinet thermistor DB display board DctH duct heater DH defrost heater DrH drain heater DT defrost timer DTh de...

Page 23: ...n Comp delay timer starts Note 2 5 minute minimum compressor on and off time Evaporator fan motor de energizes when door is open 20 minute minimum defrost time Perimeter heater controlled by perimeter heater switch Glass door GD models heater controlled by glass door heater switch RFH1 SSB HS HSE Condensate pump motor has power supply as soon as the power switch is placed in the ON position Conden...

Page 24: ... HS HSE Perimeter heater and mullion heater are controlled through the control board and turn on and off with compressor when S3 dip switch 8 is in the off position Models may utilize any combination of the following heaters Condensate Pan Heater Cord Heater Drain Heater Duct Heater and Glass Tube Heater See VII Wiring Diagrams for specific model details DTh in control DH energized Comp de energiz...

Page 25: ...rded access menu the cabinet setpoint defrost frequency and temperature display scale can be adjusted For further details see II E 1 Guarded Access Menu From the service menu information regarding appliance functions can be obtained For further details see II E 2 Service Menu 2 Display Board Layout Ribbon Cable Connector LED Display Up and Down Buttons ENTER Button RESET Button P N 2A0883 01 Front...

Page 26: ...t change wiring and connections Do not misconnect terminals Do not short out power supply to test for voltage Always replace the whole control board assembly if it goes bad Keep the thermistor clogged filter door switch and high pressure switch leads and ribbon cable at least 1 1 2 away from high voltage leads 100VAC or more to protect against electrical noise 1 Location The control box control pa...

Page 27: ...light blue Door Heater RH_ SSB GD freezer 6 Defrost Heater freezer Models may utilize any combination of the following additonal heaters Cord Heater Drain Heater Duct Heater and Glass Tube Heater See VII Wiring Diagrams for specific model details 7 Open 8 Open 9 Power Switch Input black 10 Compressor Relay gray K5 Connector 5VDC Open K4 Connector 5VDC Cabinet Thermistor gray K3 Connector 5VDC Defr...

Page 28: ...ress ENTER repeatedly until you have cycled through the menu and the appliance returns to the normal display mode If you do not cycle through the menu and no button is pressed in 15 seconds the display will return to normal and the setpoint will remain unchanged b Defrost Frequency 1a Defrost for Refrigerators Control Board Revision 22 and earlier This appliance uses an off cycle defrost When a se...

Page 29: ...e returns to the normal display mode If you do not cycle through the menu and no button is pressed in 15 seconds the display will return to normal and the defrost frequency will remain unchanged Note The change in the defrost setting will take effect after the next defrost based on the previous setting If it is desired that this change in interval timing take effect immediately turn the appliance ...

Page 30: ...un time in last 24 hours to the nearest hour Example 16 hours total run time in the last 24 hours Value is every 24 hours 5 50 Right two digits represent compressor on time percentage for the last 5 run cycles A run cycle begins when the compressor switches from off to on and ends the next time it switches from off to on See diagram below Example 50 run time over the last 5 run cycles Value is cal...

Page 31: ...f temperature 5 beeps every ten seconds Defrost Alarm Defrost has taken longer than 1 hour Control board has terminated defrost Press RESET Alarm will stop and E3 will clear If 4 consecutive defrosts take more than 1 hour a qualified service technician must be called For the service tech to reset this alarm press ALARM RESET on the control board itself E4 6 beeps every ten seconds High Pressure Al...

Page 32: ... last 45 min Freezer Defrost cycles on programmed defrost timed intervals and terminates at 45 min E10 Dual Temp Models Only 10 beeps every ten seconds Communication Alarm Freezer and refrigerator control boards not communicating properly to control compressor delay When communication is restored alarm will reset During alarm press RESET to silence buzzer for 18 hours CF 1 beep every ten seconds C...

Page 33: ...FF ON OFF ON RFH1 SSB HS HSE Freezer OFF OFF OFF OFF OFF ON OFF OFF RFH2 SSB HD Freezer Aux Code P 5 and Earlier OFF OFF OFF OFF OFF ON OFF OFF RFH2 SSB HD Freezer Aux Code P 6 and Later OFF OFF OFF OFF OFF ON ON OFF RFH3 SSB HD Freezer Aux Code P 5 and Earlier OFF OFF OFF OFF OFF ON OFF OFF RFH3 SSB HD Freezer Aux Code P 6 and Later OFF OFF OFF OFF OFF ON ON OFF NOTICE S3 Dip Switch 3 Used to acc...

Page 34: ...n 5 LBU wire when the compressor is off and de energizes when the compressor turns on Factory set no adjustment required S3 Dip Switch Setting Cabinet Light Heated Glass Door No 2 OFF Cabinet Light ON Heated Glass Door GD models c Door Switch Type S3 dip switch 3 Hoshizaki has utilized both normally open and normally closed door switch contact styles S3 dip switch 3 is used to select the type of s...

Page 35: ...Temp Models g Freezer Evaporator Fan Operation except RFH1 S3 dip switch 7 Active when S3 dip switch 1 and S3 dip switch 8 are in the OFF position freezer application When S3 dip switch 7 is in the ON position evaporator fan operates continuously except during defrost and doors open and the temperature at which the evaporator fan resumes after defrost changes from 0 F 18 C to 70 F 21 C When set to...

Page 36: ...e correctly Factory set no adjustment required Note S3 dip switch 8 is ignored when S3 dip switch 1 is in the ON position or S3 dip switch 6 is in the OFF position Model Components on CB K9 pin 2 RFH1 SSB HD Freezer Condensate Pan Heater and Drain Heater aux code Q 5 and later RFH1 SSB HS HSE Freezer Drain Heater Perimeter Heater and Mullion Heater RFH2 SSB HD and RFH3 SSB HD Condenser Fan Motor S...

Page 37: ...ergizing the compressor until the pressure returns to an acceptable level For further details see III Service Diagnosis G Perimeter Frame Heater This appliance is equipped with a perimeter frame heater This prevents the formation of condensate on the front frame of the appliance under high humidity conditions If operating the appliance under conditions where condensate will not form these heaters ...

Page 38: ... you go through the diagnostic procedure check to assure the components energize and de energize correctly If not those components or controls are suspect Always choose a neutral W wire to establish a good neutral connection when checking high voltages CB POWER OK LED remains on unless power supply is interrupted IMPORTANT The maximum allowable voltage variation is 10 percent of the nameplate rati...

Page 39: ...ontinuity 8a Cool Down Refrigerator LEDs 4 Comp and 5 ConFM are on EvapFM continues 2 5 minute Comp delay timer terminates Comp and ConFM energize 2 5 min Comp minimum run timer starts 8b Cool Down RFH1 SSB HD HS HSE Refrigerator LEDs 4 Comp and ConFM and 5 unused are on EvapFM continues 2 5 minute Comp delay timer terminates Comp and ConFM energize 2 5 min Comp minimum run timer starts a Comp Dia...

Page 40: ... GY wire to a neutral W wire If 115VAC is present and cabinet temperature has been met by 3 F 1 7 C or more replace CB If 115VAC is not present check continuity of Comp relay contacts If closed replace Comp relay a2 Comp and ConFM Diagnosis RFH1 SSB HD HS HSE Refrigerator If Comp and ConFM do not de energize check for 115VAC at CB K1 connector pin 10 GY wire to a neutral W wire If 115VAC is presen...

Page 41: ...M and 5 unused are on LED 3 EvapFM on is off DTh warms to 40 F 4 C EvapFM continues 2 5 minutes later Comp and ConFM energize a Thermistor Diagnosis Has DTh warmed to 40 F 4 C or higher Confirm DTh status see III C Thermistor Check b Comp Diagnosis Confirm that after 2 5 min Comp delay timer terminates CB LED 4 turns on and Comp energizes If not check for 115VAC at CB K1 connector pin 10 GY wire t...

Page 42: ...e Comp relay contacts are open Confirm 115VAC on Comp relay coil gray GY wire to a neutral W wire If 115VAC is present and contacts are open replace Comp relay d EvapFM Diagnosis Check that EvapFM is running If not check for 115VAC at CB K1 connector pin 3 DBU wire to a neutral W wire If 115VAC is not present replace CB If 115VAC is present check EvapFM blade for binding and EvapFM continuity Lege...

Page 43: ...ding If overload is open let overload cool and reset Replace overload if it does not reset When overload closes if Comp still does not start check start capacitor start relay and Comp motor winding b1 ConFM Diagnosis Freezer auxiliary code P 5 and earlier If ConFM does not energize check for 115VAC at CB K9 connector pin 2 BR wire to a neutral W wire If 115VAC is not present replace CB Next check ...

Page 44: ...t de energize check for 115VAC at CB K1 connector pin 10 GY wire to a neutral W wire If 115VAC is present and cabinet temperature has been met by 3 F 1 7 C or more replace CB If 115VAC is not present check continuity of Comp relay contacts If closed replace Comp relay c EvapFM Diagnosis If EvapFM does not de energize check for 115VAC at CB K1 connector pin 3 DBU wire to a neutral W wire If 115VAC ...

Page 45: ...es not de energize check for 115VAC at CB K1 connector pin 3 DBU wire to a neutral W wire If 115VAC is present replace CB f DrH PH and MH Diagnosis RFH1 SSB HS HSE Freezer If heaters do not de energize check for 115VAC at CB K9 connector pin 2 BR wire to a neutral W wire If 115VAC is present replace CB B Defrost Termination Defrost Recovery Step 1 1a Freezer auxiliary code P 5 and earlier LEDs 3 E...

Page 46: ...e CB If 115VAC is present check for 115VAC at Comp relay black BK wire and red R wire to a neutral W wire If 115VAC is not present on the black BK wire check wiring connections If 115VAC is present on black BK wire but not on the red R wire Comp relay contacts are open Confirm 115VAC on Comp relay coil gray GY wire to a neutral W wire If 115VAC is present and contacts are open replace Comp relay N...

Page 47: ...is present check EvapFM blade for binding and EvapFM continuity 8a Cool Down Freezer LEDs 4 Comp and 5 ConFM are on except RFH1 SSB HD LED 3 EvapFM on is off 2 5 min Comp delay timer terminates EvapFM continues Comp and ConFM energize 2 5 min Comp minimum run timer starts 8b Cool Down RFH1 SSB HD Freezer LED 4 Comp and ConFM is on LED 3 EvapFM on is off LED 5 CPH and DrH is on after first cool dow...

Page 48: ... 9a Cool Down Achieved Freezer auxiliary code P 6 and later No component LEDs are on LED 3 EvapFM on is off CTh cools to 3 F 1 7 C below setpoint EvapFM continues Comp and ConFM de energize 9b Cool Down Achieved RFH1 SSB HD Freezer LED 5 CPH and DrH is on LED 3 EvapFM on is off CTh cools to 3 F 1 7 C below setpoint EvapFM continues CPH and DrH energize and remain energized until power is turned of...

Page 49: ...B K1 connector pin 6 O wire to a neutral W wire again If 115VAC is not present and Comp is not energized replace CB If 115VAC is present confirm DH amperage If amperage is not present check defrost thermostat and DH continuity If amperage is present confirm that evaporator warms to 100 F 38 C at DTh location Next check DTh status See III C Thermistor Check When DTh reaches 100 F 38 C DH de energiz...

Page 50: ...on Comp relay coil gray GY wire to a neutral W wire If 115VAC is present and contacts are open replace Comp relay Next if 115VAC is present on the red R wire check continuity of Comp overload If overload is closed check start capacitor start relay and Comp motor winding If overload is open let overload cool and reset Replace overload if it does not reset When overload closes if Comp still does not...

Page 51: ...BU wire to a neutral W wire If 115VAC is not present replace CB If 115VAC is present check EvapFM blade for binding and EvapFM continuity D Defrost Termination Defrost Completion 1a Freezer auxiliary code P 6 and later LEDs 4 Comp and 5 ConFM are on LED 3 EvapFM on is off When CTh reads 15 F 8 3 C above setpoint or less cabinet temperature is displayed on DB Defrost is complete 1b FH1 SSB HD Freez...

Page 52: ...ote that the order of the LEDs from the outer edge of the board is 5 4 1 2 3 Components e g Comp cycle during the test Following the output test the appliance resumes operation If the LEDs do not light as described above CB is bad and must be replaced 4 Confirm Clogged Filter Thermostat Check for 5VDC at CB K6 connector pin 2 P wire to K5 connector pin 2 open If 5VDC is not present CB is bad and m...

Page 53: ... to the OFF position then unplug the appliance 2 Remove the control box cover 3 Remove the cabinet and defrost thermistors 4 Disconnect the cabinet thermistor gray GY wires from the RED K3 connector and the defrost thermistor orange O wires from the WHITE K3 connector 5 Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 minutes 6 Check the resistance between the w...

Page 54: ...CB is bad and must be replaced Diagnosis High Pressure Switch This may be a N O normally open or N C normally closed HPS See VII Wiring Diagrams for cut out and cut in configuration CB automatically adjusts to N O or N C HPS If HPS trips 3 times in 1 hour E4 alarm occurs on CB Press RESET on CB See II E 3 LED Lights and Alarm Safeties Chart Check that the air filter and condenser are clean Next ch...

Page 55: ...Cooling Appliance Not Cooling Possible Cause 1 Power Supply a Unplugged off blown fuse or tripped or defective circuit breaker b Loose connection c Not within specifications 2 Cord and Plug a Loose connection b Defective 3 Power Switch control box a OFF position b Bad contacts 4 Wiring a Loose connection or open b Faulty 5 Control Transformer a Defective 6 Display Board a Not communicating with co...

Page 56: ...Frequency a Not enough defrost occurring per day See II E 1 b Defrost Frequency 2 Evaporator a Dirty 3 Evaporator Fan Motor a Defective b Fan Blade Binding 4 Control Board a Defective 5 Refrigerant Charge a Low 6 Thermostatic Expansion Valve a Defective 7 Defrost Thermistor Freezer Only a Out of position or defective 8 Defrost Heater Freezer Only a Defective 9 Drain Line a Restricted 10 Defrost Dr...

Page 57: ...d store it in an approved container Do not discharge the refrigerant into the atmosphere Do not leave the system open for longer than 15 minutes when replacing or servicing parts The Polyol Ester POE oils used in R 404A applications can absorb moisture quickly Therefore it is important to prevent moisture from entering the system when replacing or servicing parts Always install a new drier every t...

Page 58: ...ng connections before unbrazing the components NOTICE Always install a new drier every time the sealed refrigeration system is opened Do not replace the drier until after all other repair or replacement has been made Install the new drier with the arrow on the drier in the direction of the refrigerant flow When brazing protect the drier by using a wet cloth to prevent the drier from overheating Do...

Page 59: ...ICE To prevent compressor damage use a throttling valve or liquid dispensing device to add the remaining liquid charge through the low side refrigerant access valve with the appliance running 9 Close the high and low side gauge manifold valves then disconnect the gauge manifold hoses 10 Cap the access valves to prevent a possible leak B Important Notes for Component Replacement NOTICE When replaci...

Page 60: ...olution Order HS 3541 that contains a motor Shinko brackets blade and all fasteners required for mounting to the shroud using the existing threaded holes For details see the appliance s parts list b Appliance s evaporator shroud has four threaded holes and a Jakel motor Solution Order a new motor Shinko brackets fan blade and the appropriate fasteners listed in the appliance s parts list Attach th...

Page 61: ... Slide the clips onto the end plate on the evaporator Install the two Support Clip C clips onto the hairpin end of the evaporator as shown in the illustration 4 Install Support Clip A and Support Clip B onto the return bend end same side as inlet and outlet tubes as shown in the illustration Note All clips are shown in the illustration in the correct orientation for installation Slide the parts on...

Page 62: ... the top pivot pin and hinge washer from the top hinge bracket 6 Firmly grasp the door and pull it forward at the top Then raise the door disengaging it from the bottom pivot pin 7 Remove the spring guide pin and spring from the spring cartridge 8 Replace the spring with one of the same color Be certain that the spring ends are engaged in both the spring cartridge and the top of the spring guide p...

Page 63: ...n any appliance is reversible as shown below The instructions for re hinging are provided in the kits listed below Convert Door Type Kit Number Right to Left Full HS 3527 Left to Right Full HS 3528 Right to Left Half HS 3529 Left to Right Half HS 3530 ...

Page 64: ...hol petroleum soap powder polishing powder alkaline cleaner acid scouring pad and especially those strong cleaners for use on a ventilating fan or a cooking range Also to prevent corrosion do not use sodium hypochlorite chlorine bleach on the stainless steel surfaces Use a clean cloth for cleaning 1 Exterior Wipe the exterior occasionally with a clean soft cloth Use a damp cloth containing a neutr...

Page 65: ...the plug or power switch with damp hands When shutting down the appliance for more than one week move the power switch to the OFF position and unplug the appliance Do not plug in unplug the appliance to start stop operation Make sure the power switch is in the OFF position before plugging in or unplugging the appliance to reduce the risk of electric shock 1 Before shutting down the appliance move ...

Page 66: ... children getting trapped Leave the shelves in place so that children may not easily climb inside This appliance contains refrigerant and must be disposed of in accordance with applicable national state and local codes and regulations Refrigerant must be recovered by properly certified service personnel ...

Page 67: ...ture Rise Clogged Filter Thermostat Control Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N O Close on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 68: ...perature Rise Control Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 69: ...Clogged Filter Thermostat Control Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N O Close on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 70: ...rature Rise Control Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 71: ...O Close on Temperature Rise Clogged Filter Thermostat Control Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N O Close on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 72: ...ol Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N O Close on Temperature Rise N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 73: ...Clogged Filter Thermostat Control Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N O Close on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 74: ...Clogged Filter Thermostat Conrol Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 75: ...Clogged Filter Thermostat Control Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N O Close on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 76: ...logged Filter Thermostat Control Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 77: ...nit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise High Pressure Switch Cut out 490 10 PSIG Cut in 370 20 PSIG Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 78: ...diagram by checking against the diagram located on the evaporator case cover High Pressure Switch Cut out 490 10 PSIG Cut in 370 20 PSIG Clogged Filter Thermostat Control Transformer Output 10VAC at 115VAC Input N O Close on Temperature Rise N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 79: ...ervicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Control Transformer Output 10VAC at 115VAC Input High Pressure Switch Cut out 490 10 PSIG Cut in 370 20 PSIG Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 80: ...Clogged Filter Thermostat NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Control Transformer Output 10VAC at 115VAC Input N O Close on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 81: ...t you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N C Open on Pressure Rise Control Transformer Output 10VAC at 115VAC Input Clogged Filter Thermostat High Pressure Switch Cut out 490 10 PSIG Cut in 370 20 PSIG Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 82: ...rature Rise N C Open on Pressure Rise Control Transformer Output 10VAC at 115VAC Input NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 83: ... Close on Temperature Rise Clogged Filter Thermostat NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Control Transformer Output 10VAC at 115VAC Input N O Close on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 84: ...perature Rise NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Control Transformer Output 10VAC at 115VAC Input N O Close on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 85: ...E Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise RFH1 SSB HD Main Wiring Power Cord Connections Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 86: ... Rise Clogged Filter Thermostat NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 87: ...Rise Clogged Filter Thermostat NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 88: ...out 270 10 PSIG Cut in 190 20 PSIG N O Close on Temperature Rise Control Transformer Output 10VAC at 115VAC Input N O Close on Pressure Rise RFH1 SSB HS HSE Main Wiring Power Cord Connections Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 89: ...gh Pressure Switch Cut out 490 10 PSIG Cut in 370 20 PSIG N O Close on Temperature Rise Control Transformer Output 10VAC at 115VAC Input N O Close on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 90: ...B HD See diagram for RH2 SSB HD See diagram for FH1 SSB HD K RFH2 SSB HD L RFH3 SSB HD NOTICE Before diagnosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover ...

Page 91: ... by checking against the diagram located on the evaporator case cover High Pressure Switch Cut out 490 10 PSIG Cut in 370 20 PSIG Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise N O Close on Temperature Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch Clogged Filter Thermostat ...

Page 92: ...checking against the diagram located on the evaporator case cover High Pressure Switch Cut out 490 10 PSIG Cut in 370 20 PSIG Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise N O Close on Temperature Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch Clogged Filter Thermostat ...

Page 93: ...roper wiring diagram by checking against the diagram located on the evaporator case cover High Pressure Switch Cut out 490 10 PSIG Cut in 370 20 PSIG Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise N O Close on Temperature Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch Clogged Filter Thermostat ...

Page 94: ...you have the proper wiring diagram by checking against the diagram located on the evaporator case cover High Pressure Switch Cut out 490 10 PSIG Cut in 370 20 PSIG Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise N O Close on Temperature Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 95: ...g diagram by checking against the diagram located on the evaporator case cover High Pressure Switch Cut out 490 10 PSIG Cut in 370 20 PSIG Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise N O Close on Temperature Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 96: ...or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise N O Close on Temperature Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 97: ...ing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N O Close on Temperature Rise Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 98: ...ing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N O Close on Temperature Rise Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 99: ...nosing and or servicing the unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover N O Close on Temperature Rise Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...

Page 100: ...unit confirm that you have the proper wiring diagram by checking against the diagram located on the evaporator case cover Clogged Filter Thermostat N O Close on Temperature Rise Control Transformer Output 10VAC at 115VAC Input N C Open on Pressure Rise Control Board Automatically Adjusts to N O or N C High Pressure Switch ...