3c) Cool Down Achieved: RFH1-SSB-HD Freezer
LED 5 (CPH and DrH (auxiliary code Q-5 and later)) is on. LED 3 (EvapFM on)
is off:
CB monitors cooling of the cabinet via CTh. CTh cools to 3
°
F (1.7
°
C) below
setpoint. EvapFM continues. Comp and ConFM de-energize. CPH and DrH (auxiliary
code Q-5 and later) energize.
4a) Cool Down Restart: Freezer (auxiliary code P-5 and earlier)
LEDs 4 (Comp) and 5 (ConFM) are on. LED 3 (EvapFM on) is off:
CTh warms
to 3
°
F (1.7
°
C) above setpoint. 2.5-minute Comp off delay timer terminates. Comp,
ConFM, and EvapFM energize.
4b) Cool Down Restart: Freezer (auxiliary code P-6 and later)
LEDs 4 (Comp) and 5 (ConFM) are on. LED 3 (EvapFM on) is off:
CTh warms
to 3
°
F (1.7
°
C) above setpoint. 2.5-minute Comp off delay timer terminates. EvapFM
continues. Comp and ConFM energize.
4c) Cool Down Restart: RFH1-SSB-HD Freezer
LEDs 4 (Comp and ConFM) and 5 (CPH and DrH (auxiliary code Q-5 and later))
are on. LED 3 (EvapFM on) is off:
CTh warms to 3
°
F (1.7
°
C) above setpoint.
2.5-minute Comp off delay timer terminates. EvapFM, CPH, and DrH (auxiliary code
Q-5 and later) continue. Comp and ConFM energize.
4d) Cool Down Restart: RFH1-SSB(-HS)(-HSE) Freezer
LEDs 4 (Comp and ConFM) and 5 (DrH, PH, and MH) are on. LED 3 (EvapFM on)
is off:
CTh warms to 3
°
F (1.7
°
C) above setpoint. 2.5-minute Comp delay timer
terminates. Comp, ConFM, EvapFM, DrH, PH and MH energize.
5a) Defrost: Freezer (auxiliary code P-5 and earlier) and RFH1-SSB(-HS)(-HSE) Freezer
(1) Time-Initiated Defrost or Manual-Initiated Defrost
a1)
Freezer (auxiliary code P-5 and earlier)–LEDs 1 (DH) and 3 (EvapFM
off) are on:
DT terminates or manual defrost initiated. 20-minute minimum
defrost timer starts. 1-hour maximum defrost timer starts. DH energizes.
"dEF" displayed on DB.
If energized, Comp, ConFM, and EvapFM de-energize.
a2)
RFH1-SSB(-HS)(-HSE) Freezer–LEDs 1 (DH) and 3 (EvapFM off) are on:
DT terminates or manual defrost initiated. 20-minute minimum defrost timer
starts. 1-hour maximum defrost timer starts. DH energizes.
"dEF" displayed on
DB. If energized, Comp, ConFM, and EvapFM de-energize. DrH, PH, and MH
de-energize.
The time-initiated defrost is factory set to 6 times per day (every 4 hours. For
further details, see "II.E.1.b) Defrost Frequency." Before changing this setting,
contact Hoshizaki Technical Support at 1-800-233-1940 for recommendations.