55
PROBLEM
POSSIBLE CAUSE
REMEDY
e) Compressor [Except
F-2000MLF]
1.
Loose connections.
1.
Tighten.
2.
Motor winding
opened or grounded.
2.
Replace.
3.
Motor Protector
tripped.
3.
Find out the cause of
overheat or
overcurrent.
f)
Power Supply
1.
Circuit Ampacity too
low.
1.
Install a larger-sized
conductor.
g) Solenoid Valve
[F-2000MLF only]
1.
Continues to leak.
1.
Check and replace.
[5] Gear Motor and
Compressor start
(for F-2000MLF, two
Solenoid Valves
open), but no ice is
produced.
a) Refrigerant Line
1.
Gas leaks.
1.
Check for leaks with a
leak detector. Reweld
leak, replace drier and
charge with
refrigerant. The
amount of refrigerant
is marked on
Nameplate or Label.
2.
Refrigerant line
clogged.
2.
Replace the clogged
component.
b) Shut-off Valves on
Condensing Unit
[F-2000MLF only]
3.
Closed.
3.
Open.
Summary of Contents for F-2000MLF
Page 14: ...14 2 CONDENSER UNIT URC 20F...
Page 16: ...16 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MLF C...
Page 17: ...17 F 2000MRF3 C F 2000MRF C...
Page 18: ...18 F 2000MWF C...
Page 20: ...20 F 2000MWF F 2000MRF C...
Page 21: ...21 F 2000MLF C...
Page 22: ...22 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MLF C...
Page 23: ...23 F 2000MRF3 C...
Page 24: ...24 F 2000MWF C...
Page 25: ...25 2 WIRING DIAGRAMS F 2000MLF C...
Page 26: ...26 F 2000MRF3 C...
Page 27: ...27 F 2000MWF C...
Page 28: ...28 F 2000MRF C...
Page 30: ...30 b When Reservoir has been filled Gear Motor starts immediately...
Page 33: ...33 e Low Water Except Water cooled Model where Compressor will operate intermittently...
Page 39: ...39...
Page 69: ...69...