14. REMOVAL AND REPLACEMENT OF BY-PASS VALVE-F-2000M#F
SERIES [EXCEPT F-2000MLF] ONLY
CAUTION
Always use a capillary tube of the same diameter and length when replacing
the by-pass lines; otherwise the performance may be reduced.
IMPORTANT
Always install a new Drier every time the sealed refrigeration system is
opened. Do not replace the Drier untill after all other repair, or replacements
have been made.
1) Turn off the power supply.
2) Remove the Front Panel.
3) Recover the refrigerant and store it in an approved container.
4) Remove the screw and the Solenoid.
5) Disconnect the By-pass Valve using brazing equipment.
6) Install the new valve.
CAUTION
Alwaye protect the valve body by using a damp cloth to prevent the valve
from overheating. Do not braze the valve body exceeding 250°F.
7) Install the new Drier.
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Evacuate the system, and charge it with refrigerant. For the water-cooled models, see
the Nameplate for the required refrigerant charge and type. For the remote air-cooled
models, see the label on the Control Box.
10) Cut the leads of the Solenoid allowing enough lead length to reconnect using closed
end connectors.
Summary of Contents for F-2000MLF
Page 14: ...14 2 CONDENSER UNIT URC 20F...
Page 16: ...16 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MLF C...
Page 17: ...17 F 2000MRF3 C F 2000MRF C...
Page 18: ...18 F 2000MWF C...
Page 20: ...20 F 2000MWF F 2000MRF C...
Page 21: ...21 F 2000MLF C...
Page 22: ...22 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MLF C...
Page 23: ...23 F 2000MRF3 C...
Page 24: ...24 F 2000MWF C...
Page 25: ...25 2 WIRING DIAGRAMS F 2000MLF C...
Page 26: ...26 F 2000MRF3 C...
Page 27: ...27 F 2000MWF C...
Page 28: ...28 F 2000MRF C...
Page 30: ...30 b When Reservoir has been filled Gear Motor starts immediately...
Page 33: ...33 e Low Water Except Water cooled Model where Compressor will operate intermittently...
Page 39: ...39...
Page 69: ...69...