background image

54

PROBLEM

POSSIBLE CAUSE

REMEDY

c)

Gear Motor
Protector (Circuit
Breaker)

1.

Tripped

1.

Find out the cause,
get rid of it, and press
Reset Button on
Circuit Breaker.

d) Gear Motor Relay

1.

Coil winding opened. 1.

Replace.

2.

Bad contacts.

2.

Check for continuity
and replace.

e) Control Timer

(Printed Circuit
Board)

1.

Broken.

1.

Replace.

f)

Gear Motor Protect
Relay

1.

Coil winding opened. 1.

Replace.

2.

Bad contacts.

2.

Check for continuity
and replace.

[4] Gear Motor starts,

but Compressor (for
Solenoid Valves) will
not start (open) or
operates (opens)
intermittently

a) Pressure Switch

[Except F-2000MLF]

1.

Dirty Air Filter or
Condenser.

1.

Clean.

2.

Ambient or
condenser water
temperature too
warm.

2.

Get cooler.

3.

Condenser water
pressure too low or
off. (Water-cooled
model only)

3.

Check and get
recommended
pressure.

4.

Water Regulating
Valve set too high.
(Water-cooled model
only)

4.

Adjust it lower.

5.

Fan not rotating.

5.

See "3. [1] a) Fan
Motor."

6.

Refrigerant
overcharged.

6.

Recharge.

7.

Refrigerant line or
components
plugged.

7.

Clean and replace
drier.

8.

Bad contacts.

8.

Check for continuity
and replace.

9.

Loose connections.

9.

Tighten.

b) X2 Relay on Control

Timer

1.

Bad contacts.

1.

Replace.Check for
continuity and replace.

2.

Coil winding opened. 2.

Replace Timer.

c)

Starter [Except three
phase model and
F-2000MLF]

1.

Bad contacts.

1.

Check for continuity
and replace.

2.

Coil winding opened. 2.

Replace.

3.

Loose Connections.

3.

Tighten.

d) Start Capacitor or

Run Capacitor
[Except three phase
model and
f-2000MLF]

1.

Defective.

1.

Replace.

Summary of Contents for F-2000MLF

Page 1: ...SERVICEMANUAL ISSUED AUG 29 2001 MODEL HOSHIZAKI MODULAR FLAKER F 2000MLF C F 2000MWF C F 2000MRF C F 2000MRF3 C NO 73099 DEC 16 2003 REVISED...

Page 2: ...of the problem IMPORTANT Only qualified service technicians should attempt to service or maintain this icemaker No such service or maintenance should be undertaken until the technician has thoroughly...

Page 3: ...10 F 2000MWF C 11 F 2000MRF 12 F 2000MRF C 13 2 CONDENSER UNIT URC 20F 14 II GENERAL INFORMATION 16 1 CONSTRUCTION 16 F 2000MLF C 16 F 2000MRF3 C F 2000MRF C 17 F 2000MWF C 18 2 CONTROL BOX LAYOUT 19...

Page 4: ...LACEMENT OF COMPRESSOR EXCEPT F 2000MLF C 61 4 REMOVAL AND REPLACEMENT OF DRIER EXCEPT F 2000MLF C 62 5 REMOVAL AND REPLACEMENT OF EXPANSION VALVE 63 6 REMOVAL AND REPLACEMENT OF WATER REGULATING VALV...

Page 5: ...5 VII CLEANINGANDMAINTENANCEINSTRUCTIONS 76 1 PREPARING THE ICEMAKER FOR LONG STORAGE 76 2 CLEANINGINSTRUCTIONS 77 3 MAINTENANCEINSTRUCTIONS 82...

Page 6: ...REFRIGERATION Suction line 1 1 16 12 UNF Fitting 10 AEROQUIP CIRCUIT Liquid line 5 8 18 UNF Fitting 6 AEROQUIP ICE MAKING SYSTEM Auger type HARVESTING SYSTEM Direct Driven Auger 400 W Gear Motor ICE...

Page 7: ...ION Suction line 1 1 16 12 UNF Fitting 10 AEROQUIP CIRCUIT Liquid line 5 8 18 UNF Fitting 6 AEROQUIP ICE MAKING SYSTEM Auger type HARVESTING SYSTEM Direct Driven Auger 400 W Gear Motor ICE MAKING WATE...

Page 8: ...ge line 1 1 16 12 UNF Fitting 10 AEROQUIP CIRCUIT Liquid line 5 8 18 UNF Fitting 6 AEROQUIP ICE MAKING SYSTEM Auger type HARVESTING SYSTEM Direct Driven Auger 400 W Gear Motor ICE MAKING WATER CONTROL...

Page 9: ...1 1 16 12 UNF Fitting 10 AEROQUIP CIRCUIT Liquid line 5 8 18 UNF Fitting 6 AEROQUIP ICE MAKING SYSTEM Auger type HARVESTING SYSTEM Direct Driven Auger 400 W Gear Motor ICE MAKING WATER CONTROL Float S...

Page 10: ...IONS ELECTRIC Permanent Connection WATER SUPPLY Inlet 1 2 FPT Cond Inlet 1 2 FPT DRAIN Outlet 3 4 FPT Cond Outlet 1 2 FPT ICE MAKING SYSTEM Auger type HARVESTING SYSTEM Direct Driven Auger 400 W Gear...

Page 11: ...CTIONS ELECTRIC Permanent Connection WATER SUPPLY Inlet 1 2 FPT Cond Inlet 1 2 FPT DRAIN Outlet 3 4 FPT Cond Outlet 1 2 FPT ICE MAKING SYSTEM Auger type HARVESTING SYSTEM Direct Driven Auger 400 W Gea...

Page 12: ...charge line 1 1 16 12 UNF Fitting 10 AEROQUIP CIRCUIT Liquid line 5 8 18 UNF Fitting 6 AEROQUIP ICE MAKING SYSTEM Auger type HARVESTING SYSTEM Direct Driven Auger 400 W Gear Motor ICE MAKING WATER CON...

Page 13: ...ischarge line 1 1 16 12 UNF Fitting 10 AEROQUIP CIRCUIT Liquid line 5 8 18 UNF Fitting 6 AEROQUIP ICE MAKING SYSTEM Auger type HARVESTING SYSTEM Direct Driven Auger 400 W Gear Motor ICE MAKING WATER C...

Page 14: ...14 2 CONDENSER UNIT URC 20F...

Page 15: ...9 mm REFRIGERANT CHARGE URC 20F R404A 7 lbs 11 oz 3500 g WEIGHT Net 104 lbs 47 kg Shipping 115 lbs 52 kg CONNECTIONS REFRIGERANT One Shot Couplings Aeroquip ELECTRICAL Permanent Connection CONDENSER A...

Page 16: ...16 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MLF C...

Page 17: ...17 F 2000MRF3 C F 2000MRF C...

Page 18: ...18 F 2000MWF C...

Page 19: ...19 2 CONTROL BOX LAYOUT F 2000MRF3 C Note The above component names are identical with the Wiring Label but not with the Parts List...

Page 20: ...20 F 2000MWF F 2000MRF C...

Page 21: ...21 F 2000MLF C...

Page 22: ...22 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MLF C...

Page 23: ...23 F 2000MRF3 C...

Page 24: ...24 F 2000MWF C...

Page 25: ...25 2 WIRING DIAGRAMS F 2000MLF C...

Page 26: ...26 F 2000MRF3 C...

Page 27: ...27 F 2000MWF C...

Page 28: ...28 F 2000MRF C...

Page 29: ...29 3 SEQUENCE OF ELECTRICAL CIRCUIT a When Power Switch is moved to ON position and Flush Switch to ICE position water starts to be supplied to Reservoir...

Page 30: ...30 b When Reservoir has been filled Gear Motor starts immediately...

Page 31: ...31 c Compressor starts F 2000MLF C only two solenoid valves open about 60 sec after Gear Motor starts...

Page 32: ...32 d Bin Control operates and about 6 sec later Compressor and Gear Motor stop simultaneously F 2000MLF two solenoid valves close...

Page 33: ...33 e Low Water Except Water cooled Model where Compressor will operate intermittently...

Page 34: ...34 f When Flush Timer operates for 15 min every 12 hours or when Flush Switch is moved to FLUSH position Flush Water Valve opens and flushes Reservoir and Evaporator...

Page 35: ...ines when 208 230V are supplied to Circuit Protect Relay it protects the circuit from being miswired If the power supply is properly connected the contact of Circuit Protect Relay does not move even w...

Page 36: ...36 h When Pressure Switch opens power supply to the control board is cut off causing the Compressor and Gear Motor to turn off immediately...

Page 37: ...6 FLUSH TIMER 7 FLUSH SWITCH 8 FLUSH WATER VALVE 9 BIN CONTROL 10 GEAR MOTOR RELAY 11 GEAR MOTOR 12 FAN MOTOR 13 COMPRESSOR OR TWO SOLENOID VALVES 2000MLF C 14 PRESSURE SWITCH 15 HEATER ON OFF ON OFF...

Page 38: ...9 BIN CONTROL 10 GEAR MOTOR RELAY 11 GEAR MOTOR 12 FAN MOTOR 14 PRESSURE SWITCH 15 HEATER ON OFF ON OFF ON OFF ON OFF ON OFF 1 2 2 3 FLUSH ICE ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF U...

Page 39: ...39...

Page 40: ...BIN CONTROL 10 GEAR MOTOR RELAY 11 GEAR MOTOR 12 FAN MOTOR 14 PRESSURE SWITCH 15 HEATER ON OFF ON OFF ON OFF ON OFF ON OFF 1 2 2 3 FLUSH ICE ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF UP...

Page 41: ...41 16 SPOUT CONTROL RELAY ON OFF 17 THERMOSTAT CONTROL 2000MWE ON OFF Compressor Discharge Temp 203 F Compressor Discharge Temp 225 F...

Page 42: ...814 TOTAL 90 211 798 207 785 202 764 gal day m3 day 100 198 748 194 733 180 680 EVAPORATOR OUTLET TEMP 70 12 11 12 11 12 11 F C 80 12 11 12 11 12 11 90 12 11 12 11 14 10 100 14 10 14 10 14 10 HEAD PRE...

Page 43: ...90 188 710 185 699 182 687 gal day m3 day 100 180 680 177 669 149 565 EVAPORATOR OUTLET TEMP 70 12 11 12 11 12 11 F C 80 12 11 12 11 12 11 90 12 11 12 11 14 10 100 14 10 14 10 14 10 HEAD PRESSURE 70...

Page 44: ...0 EVAPORATOR OUTLET TEMP 70 14 10 14 10 14 10 F C 80 14 10 14 10 14 10 90 14 10 14 10 16 9 100 16 9 16 9 16 9 HEAD PRESSURE 70 219 15 4 219 15 4 219 15 4 80 230 16 2 230 16 2 230 16 2 90 241 16 9 241...

Page 45: ...EVAPORATOR OUTLET TEMP 70 12 11 12 11 14 10 F C 80 14 10 14 10 14 10 90 14 10 14 10 14 10 100 14 10 14 10 14 10 HEAD PRESSURE 70 222 15 6 222 15 6 222 15 6 80 225 15 8 225 15 8 225 15 8 90 228 16 0 2...

Page 46: ...11 12 11 12 11 12 F C 80 11 12 11 12 11 12 90 11 12 11 12 11 12 100 11 12 11 12 11 12 HEAD PRESSURE 70 262 18 4 263 18 5 265 18 6 80 262 18 4 263 18 5 265 18 6 90 262 18 4 263 18 5 265 18 6 PSIG kg sq...

Page 47: ...70 10 12 10 12 12 11 F C 80 10 12 10 12 12 11 90 10 12 10 12 12 11 100 10 12 10 12 12 11 HEAD PRESSURE 70 262 18 4 263 18 5 266 18 7 80 262 18 4 263 18 5 266 18 7 90 262 18 4 263 18 5 266 18 7 PSIG k...

Page 48: ...VAPORATOR OUTLET TEMP 70 12 11 12 11 12 11 F C 80 12 11 12 11 12 11 90 12 11 12 11 14 10 100 14 10 14 10 14 10 HEAD PRESSURE 70 221 15 5 221 15 5 221 15 5 80 230 16 1 230 16 1 230 16 1 90 238 16 8 238...

Page 49: ...EVAPORATOR OUTLET TEMP 70 12 11 12 11 12 11 F C 80 12 11 14 10 14 10 90 14 10 14 10 14 10 100 14 10 14 10 14 10 HEAD PRESSURE 70 220 15 5 220 15 5 220 15 5 80 227 15 9 227 15 9 227 15 9 90 233 16 4 23...

Page 50: ...side line of the system Or prepare a thermometer to check the condenser drain temperature 2 Rotate the Adjustment Screw by using a flat blade screwdriver so that the pressure gauge shows 260 PSIG R 40...

Page 51: ...er according to the following procedures 1 Remove the Bolt 2 Take off the upper Cutter Head of the two coarse flakes or set the upper Cutter Head on the lower fine flakes The unit is shipped from the...

Page 52: ...etting if necessary according to the following instructions 1 Remove the Cap from the E P R Access Valve and connect a pressure gauge The E P R needs no adjustment if the pressure gauge shows 22 PSIG...

Page 53: ...alve 1 Coil winding opened 1 Replace i Shut off Valve 1 Closed 1 Open 2 Water failure 2 Wait till water is supplied j Plug and Receptacle Control Box 1 Disconnected 1 Connect 2 Terminal out of Plug or...

Page 54: ...r water temperature too warm 2 Get cooler 3 Condenser water pressure too low or off Water cooled model only 3 Check and get recommended pressure 4 Water Regulating Valve set too high Water cooled mode...

Page 55: ...uctor g Solenoid Valve F 2000MLF only 1 Continues to leak 1 Check and replace 5 Gear Motor and Compressor start for F 2000MLF two Solenoid Valves open but no ice is produced a Refrigerant Line 1 Gas l...

Page 56: ...sure too low or off Water cooled model only 3 Check and get recommended pressure 4 Fan rotating too slow 4 See 3 1 a Fan Motor 5 Water Regulating Valve clogged Water cooled model only 5 Clean 6 Conden...

Page 57: ...is found hard by testing install a softener f Evaporator Pressure Regulator F 2000MLF only 1 Low side pressure too low 1 Check Evaporator Pressure Regulator and adjust or replace it if necessary 2 Ov...

Page 58: ...fold Hoses to the high side low side and Evaporator Pressure Regulator E P R access ports to purge or evacuate the unit To recharge the system simply open the Suction and Liquid Line Shut off Valves a...

Page 59: ...o loosen the connection and purge the air from the Hose See the Nameplate for the required refrigerant charge Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Stan...

Page 60: ...rant and store it in an approved container Do not discharge the refrigerant into the atmosphere 4 Do not use silver alloy or copper alloy containing Arsenic 5 Do not use R 404A as a mixture with press...

Page 61: ...on and Access Pipes from the Compressor using brazing equipment WARNING When repairing a refrigerant system be careful not to let the burner flame contact any electrical wires or insulation 5 Remove t...

Page 62: ...after all other repair or replacements have been made 1 Turn off the power supply and remove the panels 2 Recover the refrigerant and store it in an approved container if required by an applicable la...

Page 63: ...VE IMPORTANT Sometimes moisture in the refrigerant circuit exceeds the Drier capacity and freezes up at the Expansion Valve Always install a new Drier every time the sealed refrigeration system is ope...

Page 64: ...container 3 Disconnect the Capillary Tube using brazing equipment 4 Disconnect the Flare connections of the valve 5 Remove the screws and the valve from the Bracket 6 Install the new valve and braze t...

Page 65: ...and store it in an approved container 4 Remove the C P R using brazing equipment 6 Braze the new C P R with nitrogen gas flowing at the pressure of 3 4 PSIG WARNING Always protect the valve body by us...

Page 66: ...Remove the Rubber O ring and the Nylon Ring at the top of the Evaporator EXTRUDING HEAD 10 Remove the three Socket Head Cap Screws and lift off the Extruding Head 11 Replace the Bearing inside the Ex...

Page 67: ...orator BEARING LOWER AND MECHANICAL SEAL 20 The Mechanical Seal consists of two parts One moves along with the Auger and the other is fixed on the Bearing Lower If the contact surfaces of these two pa...

Page 68: ...g at a pressure of 3 4 PSIG b Replace the Drier except F 2000MLF c Check for leaks using nitrogen gas 140 PSIG and soap bubbles d Evacuate the system Charge it with refrigerant except F 2000MLF For th...

Page 69: ...69...

Page 70: ...off the power supply remove the panels and close the Water Supply Line Shut off Valve 2 Disconnect the terminals from the Control Water Valve 3 Loosen the Fitting Nut on the Control Water Valve Inlet...

Page 71: ...5 Remove the Drain Pipe from the Flush Water Valve 6 Connect the Drain Pipe to the new Flush Water Valve and place the valve in position 7 Connect the Hose to the Flush Water Valve and secure it with...

Page 72: ...ways protect the valve body by using a damp cloth to prevent the valve from overheating Do not braze with the valve body exceeding 250 F 8 Check for leaks using nitrogen gas 140 PSIG and soap bubbles...

Page 73: ...equipment 6 Braze the new E P R with nitrogen gas flowing at a pressure of 3 4 PSIG WARNING Always protect the E P R by using a damp cloth to prevent the E P R from overheating Do not braze with the...

Page 74: ...tore it in an approved container 4 Remove the screw and the Solenoid 5 Disconnect the By pass Valve using brazing equipment 6 Install the new valve CAUTION Alwaye protect the valve body by using a dam...

Page 75: ...75 11 Connect the new Solenoid leads 12 Attach the Solenoid to the valve body and secure it with a screw 13 Replace the panels in their correct position 14 Turn on the power supply...

Page 76: ...peratures using air or carbon dioxide Shut off the icemaker until the proper ambient temperature is resumed Remote Air cooled Models 1 Run the icemaker with the Water Supply Line Shut off Valve closed...

Page 77: ...r conditions 2 To prevent injury to individuals and damage to the icemaker do not use ammonia type cleaners 3 Always wear liquid proof gloves for safe handling of the cleaning and sanitizing solution...

Page 78: ...r Valve in their correct positions Note This unit is designed to start operating when the Reservoir is filled with water 12 Move the Flush Switch to the ICE position 13 Replace the Top Panel and the F...

Page 79: ...ly and make ice using the solution until the icemaker stops icemaking 9 Remove the Front Panel 10 Move the Flush Switch to the FLUSH position to drain the sanitizing solution 11 Move the Flush Switch...

Page 80: ...mble the Bin Control Assembly by removing the two Snap Pins Shaft and Activator 8 Remove the two Thumbscrews Spout Switch Cover Spout Switch and Actuator 9 Remove the three Thumbscrews and the Spout 1...

Page 81: ...d with the icemaker 2 To have the optimum performance of this icemaker the following consumable parts need periodic inspection maintenance and replacement Extruding Head Housing Gear Motor Auger Mecha...

Page 82: ...scoopprovided Binaccessory The Storage Bin is for ice use only Do not store anything else in the bin Keep the scoop clean Clean using a neutral cleaner and rinse thoroughly Clean the bin liner using a...

Reviews: