63
1) Turn off the power supply, and remove the panels.
2) For F-2000MLF, close the Shut-off Valves to the Compressor Rack Assembly.
3) Recover the refrigerant and store it in an approved container, if required by an applicable
law.
4) Remove the Expansion Valve Bulb at the Evaporator outlet.
5) Remove the Expansion Valve Cover, and remove the Expansion Valve using brazing
equipment.
6) Braze the new Expansion Valve with nitrogen gas flowing at the pressure of 3 - 4 PSIG.
WARNING
Always protect the valve body by using a damp cloth to prevent the valve
from overheating. Do not braze with the valve body exceeding 250°F.
5. REMOVAL AND REPLACEMENT OF EXPANSION VALVE
IMPORTANT
Sometimes moisture in the refrigerant circuit exceeds the Drier capacity
and freezes up at the Expansion Valve. Always install a new Drier every
time the sealed refrigeration system is opened. Do not replace the Drier
until after all other repairs or replacements have been made.
7) Install the new Drier [except F-2000MLF].
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Evacuate the system. Charge it with refrigerant [except F-2000MLF]. For the water-
cooled models, see the Nameplate for the required refrigerant charge and type. For the
remote air-cooled models, see the label on the Control Box.
10) Attach the Bulb to the suction line. Be sure to secure the Bulb using a band and
to insulate it.
11) Place the new set of Expansion Valve Covers in position.
12) For F-2000MLF, open the Shut-off Valves to the Compressor Rack Assembly.
Summary of Contents for F-2000MLF
Page 14: ...14 2 CONDENSER UNIT URC 20F...
Page 16: ...16 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MLF C...
Page 17: ...17 F 2000MRF3 C F 2000MRF C...
Page 18: ...18 F 2000MWF C...
Page 20: ...20 F 2000MWF F 2000MRF C...
Page 21: ...21 F 2000MLF C...
Page 22: ...22 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MLF C...
Page 23: ...23 F 2000MRF3 C...
Page 24: ...24 F 2000MWF C...
Page 25: ...25 2 WIRING DIAGRAMS F 2000MLF C...
Page 26: ...26 F 2000MRF3 C...
Page 27: ...27 F 2000MWF C...
Page 28: ...28 F 2000MRF C...
Page 30: ...30 b When Reservoir has been filled Gear Motor starts immediately...
Page 33: ...33 e Low Water Except Water cooled Model where Compressor will operate intermittently...
Page 39: ...39...
Page 69: ...69...