VI. REMOVAL AND REPLACEMENT OF COMPONENTS
1. SERVICE FOR REFRIGERANT LINES
[a] REFRIGERANT RECOVERY [EXCEPT F-2000MLF(-C)]
The icemaker unit is provided with two Refrigerant Access Valves - one on the low-side
and one on the high-side line. Using proper refrigerant practices recover the refrigerant
from the Access Valves and store it in an approved container. Do not discharge the refrig-
erant into the atmosphere.
[b] REFRIGERANT RECOVERY [F-2000MLF ONLY]
The refrigerant charge on the F-2000MLF is provided from the external Compressor Rack
Assembly. In the event that service is required on the F-2000MLF, close the Suction and
Liquid Line Shut-off Valves located at the rear of the unit. Attach the Service Manifold
Hoses to the high side, low side and Evaporator Pressure Regulator (E.P.R.) access ports
to purge or evacuate the unit. To recharge the system, simply open the Suction and Liquid
Line Shut-off Valves after evacuating the F-2000MLF.
[c] EVACUATION AND RECHARGE [R-404A]
1) Attach Charging Hoses, a Service Manifold and a Vacuum Pump to the system. Be
sure to connect Charging Hoses to both High-side and Low-side Access Valves.
IMPORTANT
Ensure all components, fasteners and thumbscrews are securely in place
after the equipment is serviced.
IMPORTANT
1. The Polyolester (POE) oils used in R-404A units can absorb moisture
quickly. Therefore it is important to prevent moisture from entering the
system when replacing or servicing parts.
2. Always install a new filter drier every time the sealed refrigeration system
is opened.
3. Do not leave the system open for longer than 15 minutes when replacing or
servicing parts.
Summary of Contents for F-2000MLF
Page 14: ...14 2 CONDENSER UNIT URC 20F...
Page 16: ...16 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MLF C...
Page 17: ...17 F 2000MRF3 C F 2000MRF C...
Page 18: ...18 F 2000MWF C...
Page 20: ...20 F 2000MWF F 2000MRF C...
Page 21: ...21 F 2000MLF C...
Page 22: ...22 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MLF C...
Page 23: ...23 F 2000MRF3 C...
Page 24: ...24 F 2000MWF C...
Page 25: ...25 2 WIRING DIAGRAMS F 2000MLF C...
Page 26: ...26 F 2000MRF3 C...
Page 27: ...27 F 2000MWF C...
Page 28: ...28 F 2000MRF C...
Page 30: ...30 b When Reservoir has been filled Gear Motor starts immediately...
Page 33: ...33 e Low Water Except Water cooled Model where Compressor will operate intermittently...
Page 39: ...39...
Page 69: ...69...