XYR301E Wireless Ethernet
User Manual
Page 72
April 2012
Connecting two separate networks together
LAN A
Configuration
In this example, network A is connected to the internet via a router at IP address 192.168.0.1.
Devices on LAN A that only require access to devices on LAN A and B, should have their gateway IP address set to
the XYR301-E Access Point as 192.168.0.200.
Devices on LAN A, that must interact with devices on LAN A and B and the internet should set the internet router
192.168.0.1 as their gateway, and must have a routing rule established for devices on Network B. On PCs, this may be
achieved with the MS-DOS command ROUTE. For this example use: ROUTE ADD 169.254.102.0 MASK
255.255.255.0 192.168.0.200. For more information on the DOS “Route” command see section 4.3 “
Error! Reference
source not found.
”
LAN B Configuration
All devices on LAN B should be configured so their gateway IP address is that of the XYR301-E Access Point as
169.254.102.54
Access Point Configuration
Connect straight through Ethernet cable between PC and XYR301-E.
Ensure configuration PC and XYR301-E are setup to communicate on the same network
Set dipswitch to SETUP
Power up unit, and wait for LINK led to cease flashing.
Adjust PC network settings
Set Configuration PC network card with network setting of IP address 192.168.0.1, netmask 255.255.255.0
Open configuration webpage with Internet Explorer at address 192.168.0.1XX/
When prompted for password, enter default username “user” and password “user”
Enter “Network”, and select Operating Mode as Access Point.
Device Mode should be set to Router.
Set the Gateway IP address to 192.168.0.1
Set the Ethernet IP address to 192.168.0.200, network mask 255.255.255.0
Set the Wireless IP address to 169.254.102.54, network mask 255.255.255.0
Select the Radio Encryption required, and enter encryption keys or passphrase if necessary.
Set dipswitch to RUN.
Click on button Save to Flash and Reset. Webpage will display that message indicating details are being written to
flash. Wait for XYR301-E to reboot before removing power. Enter a System Generator String
Client Configuration
Perform the same configuration steps as the Access Point configuration with the following differences:
Enter “Network”, and select Operating Mode as Client.
Device Mode should be set to Bridge.
Set the Gateway IP address to 169.254.102.54
Set the Ethernet IP address to 169.254.102.53, network mask 255.255.255.0
Set the Wireless IP address to 169.254.102.53, network mask 255.255.255.0
Click on button Save to Flash and Reset. Webpage will display that message indicating details are being written to
flash. Wait for XYR301-E to reboot before removing power.
Summary of Contents for XYR301E
Page 2: ...Page ii April 2012 ...
Page 18: ......