NOTES:
• The SV2 Series valves have internal algorithms that prevent the accidental or intentional removing of the Pressure
Module once the valve has been fully setup and is in use.
–
If the installed/operational Pressure Module connector is disconnected and reconnected, a 19-Pressure Module
reading fault will occur and can be cleared via the valve reset button.
–
When a Pressure Module is replaced on the valve, two lockouts will occur; 19-Pressure Module reading fault and 22-
Lo-/Hi-Gas pressure not configured.
₀
The faults cannot be fully cleared until the new Pressure Module is Accepted and the Hi-Gas/Lo-Gas Limits and/or
VPS are re-programmed.
₀
Note that the previously selected Lockout Type for the Hi-Gas/Lo-Gas Limits remain intact as well as the VPS setup,
but the Limit Setpoints are deleted and must be setup in order to make the Limits operational.
• To avoid the 2 lockout conditions mentioned above when replacing a Pressure Module:
–
BEFORE installing the replacement Pressure Module, disable the Hi-Gas and Lo-Gas Lockout Types and the Valve
Proving Sequence (VPS)
–
Perform the Verify Safety Parameters procedure to confirm the changes.
–
Replace the Pressure Module and plug in the electrical connector.
To make the valve operational:
–
Accept the new Pressure Module and serial number either via the Guided Valve Set Up or the Pressure Module tab in
the Setup & Tests / Settings menus.
₀
If this step is not performed, 3 faults will occur upon entering the Hi-Gas/Lo-Gas Pressure or VPS setup screens. In
order to allow setup functions, the Pressure Module must be Accepted and the valve reset button pushed.
–
Perform the Pressure Module setup procedures for Hi-Gas Pressure, Lo-Gas Pressure and/or VPS again to ensure
proper setup, since the original Limit Setpoints will be deleted.
–
Perform the Safety Parameters Verification procedure before the Pressure Module features and the valve will be
operational.
Flanges
Specifications
Models:
Valve size: 1 inch (DN25)
Flange sizes: ½, ¾, 1 and 1 ¼ in NPT or BSPP
DN15, 20, 25, 32
Valve sizes: 1 ½ and 2 in (DN40 and DN50)
Flange sizes: 1, 1 ¼, 1 ½, 2 in NPT or BSPP
DN25, 32, 40, 50
Flange pressure tap sizes & threads:
NPT flanges: 1/8-27” (3mm) NPT. Torque 7±1 Nm (62±9 in-lbf).
BSP flanges: 1/8-28” (3mm) BSP. Torque 1.5±0.15 Nm (13.3±1.3 in-lbf).
Mounting:
1 inch (DN25) valves: Four (4) M5x16 Hex head screws
1 ½, 2 inch (DN40/50) valves: Four (4) M8x20 Hex head screws
Maximum tightening torque
1 inch (DN25) valves: 3.4 Nm (30 in-lbf)
1 ½, 2 inch (DN40/50) valves: 13.5-14.5 Nm (120-128 in-lbf)
Documentation:
32-00028, AB Valve Flange Kits Installation Instructions
32-00036, CD Valve Flange Kits Installation Instructions
MCR37127