SV2 Series Safety Shut-off Valves
219
V2F, V2V
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Address
Type
Valve
Model
Intelligence
Levels
Description
Data
Type
Content
Dec
Hex
243
F3
General
All
Standard
Valve factory data
62 x Char
Main electronics factory data string of characters ended by
either ASCII-0 or end of register array.
Two characters per register
244
F4
Valve factory data
62 x Char
245
F5
Valve factory data
62 x Char
246
F6
Valve factory data
62 x Char
Main electronics factory data string of characters ended by
either ASCII-0 or end of register array.
Two characters per register
247
F7
Valve factory data
62 x Char
248
F8
Valve factory data
62 x Char
249
F9
Valve factory data
62 x Char
250
FA
Valve factory data
62 x Char
251
FB
Valve factory data
62 x Char
252
FC
Valve factory data
62 x Char
253
FD
Valve factory data
62 x Char
254
FE
Valve factory data
62 x Char
255
FF
Valve factory data
62 x Char
24
18
HGP / LGP
All
Standard
Minimum applicable pressure range for Pressure
Module used.
Shown in user selected pressure units.
U16
Pressure.
See Holding Register 74 for selected units.
25
19
Maximum applicable pressure range for Pressure
Module used.
Shown in user selected pressure units.
U16
Pressure.
See Holding Register 74 for selected units.
63
3F
Hi-/Lo-Gas Pressure function status
Enum
0 =HGP and LGP function disabled
1 =HGP and/or LGP function enabled; no
pressure setup has been performed
2 =HGP and/or LGP function enabled; pressure
is within requested limits
0x10 =In commissioning mode
0x20 =In HGP/LGP test mode
0x81 =Invalid HGP and/or LGP parameters
0x82 =Detected pressure lower than Lo-Gas
limit setting
0x83 =Detected pressure higher than Hi-Gas
limit setting
64
40
Operating pressure value stored for Low gas
pressure (LGP) limit setpoint during setup as
measured during maximum burner firing rate.
Shown in user selected pressure units.
U16
Pressure.
See Holding Register 74 for selected units.
0=Invalid value
65
41
Operating pressure value stored for High gas
pressure (HGP) limit setpoint during setup as
measured during minimum burner firing rate.
Shown in user selected pressure units.
U16
Pressure.
See Holding Register 74 for selected units.
0=Invalid value